25. Clear high starter voltage relay -702 and -712 only
When the auxiliary voltage falls below this value, the relay will open (after a delay, depending
on setting 14 and/or 15). This value needs to be less than or equal to the previous parameter.
Default
0 V
_______________________________________________________________
26. High temperature relay -702 and -712 only
When the battery temperature rises above this value for more than 10 seconds, the relay will
be activated.
______________________________________________________________
27. Clear high temperature relay -702 and -712 only
When the temperature falls below this value, the relay will open (after a delay, depending on
setting 14 and/or 15). This value needs to be less than or equal to the previous parameter.
______________________________________________________________
28. Low temperature relay -702 and -712 only
When the temperature falls below this value for more than 10 seconds, the relay will be
activated.
______________________________________________________________
29. Clear low temperature relay -702 and -712 only
When the temperature rises above this value, the relay will open (after a delay, depending on
setting 14 and/or 15). This value needs to be greater than or equal to the previous parameter.
See setting 67 for choosing between °C and °F.
Default
0 °C
0 °F
_______________________________________________________________
30. Mid voltage relay -702 and -712 only
When the midpoint voltage deviation rises above this value for more than 10 seconds, the
relay will be activated. See section 5.2 for more information about the midpoint voltage.
______________________________________________________________
31. Clear mid voltage relay -702 and -712 only
When the midpoint voltage deviation falls below this value, the relay will open (after a delay,
depending on setting 14 and/or 15). This value needs to be less than or equal to the previous
parameter.
Default
0 %
Range
0 – 95 V
Range
-40 – 99 °C
-40 – 210 °F
Range
0 – 99 %
25
Step size
0.1 V
Step size
1 °C
1 °F
Step size
0.1 %