Approved Venting Method 1: Through the Wall Factory Built Chimney 
 
 
 
 
 
 
 
 
Storm Collar 
 
 
 
Roof Flashing 
 
 
 
 
 
Wall Thimble 
 
 
Chimney Connector 
(Single or Double Wall) 
 
 
 
Prefabricated chimney systems must conform to UL‐103HT (2100 °F) for the U.S. and ULC‐S629 (650°C) for 
Canada. 
This wood burning unit is only listed for installation with 6.0" diameter chimney connector and chimney systems. 
Installing this unit on prefabricated chimneys larger than 6.0" diameter will result in decreased draft and the  
potential for poor unit performance. 
Follow all venting system manufacturer's installation requirements and required clearances. 
Use three sheet metal screws at each single wall chimney connector joint (check manufacturer's 
recommendations when double wall chimney connector is used). 
Drill three holes in the flue collar of the unit and attach the chimney connector to the unit using sheet metal 
screws (holes should be pre‐drilled in flue collar from factory). 
Properly attach the prefabricated chimney system to the home in strict accordance with the prefabricated 
chimney system manufacturer's instructions. 
Avoid numerous elbows and excessive horizontal runs as both will lead to poor draft and increased creosote 
accumulation.   Horizontal runs of chimney connector must never exceed 4.0 ft. and the overall length of the 
chimney connector must not exceed 8.0 ft. 
Special adapters and slip connectors are available to eliminate the need to cut single wall chimney connector. 
Double wall chimney connector must be used with these slip connectors, as it cannot be trimmed to length. 
 
 
.
Please Note: Installation diagrams are for reference purposes only and are not drawn to scale, nor meant to be used as 
plans for each individual installation. Please follow all venting system requirements, maintain the required clearances to combustibles, 
INSTALLATION 
10 ft. 
and follow all local codes 
 
Termination Cap 
The 10‐3‐2 Rule: The chimney system 
must terminate 3.0 ft. above the point 
where its centerline passes through the 
roof AND the chimney must terminate 
2.0 ft. above any part of the dwelling  
within a 10 ft. radius of the chimney. 
Class A Chimney System 
Tee and Tee Support 
Page | 11