INSTALLATION INSTRUCTIONS
C-PHB-C-L2F-SCCT Series
With Emergency Backup
FIGURE 8
ELECTRICAL CONNECTIONS
Fixture is equipped with a universal volt driver 120-277V
NOTE: Make sure voltage range of fixture is compatible with supply
voltage
NOTE: The emergency driver must be fed from the same branch as the
AC driver.
PHASE TO NEUTRAL WIRING 120/277V
1. Connect supply ground to fixture ground (green) lead.
2. Connect supply common to fixture neutral (white) lead.
3. Connect supply Vin (unswitched) to the fixture hot black
(unswitched) lead.
4. Connect supply Vin (switched) to the fixture hot black
(switched) lead.
Tuck all wires carefully into wiring chamber ensuring that no wires
are pinched.
PHASE TO PHASE WIRING 208/240V
1. Connect supply ground to fixture ground (green) lead.
2. Connect supply Hot 1 (unswitched) to the fixture black
(unswitched) lead.
3. Connect supply Hot 1 (switched) to the fixture black
(switched) lead.
4. Connect supply Hot 2 to the fixture white lead.
Tuck all wires carefully into wiring chamber ensuring that no wires
are pinched.
DIMMING
NOTE: When occupancy sensor is used, dimming is controlled by oc-
cupancy sensor.
1. Grey or pink (-) and violet (+) leads are for 0-10V dimming
systems. Cap off if not used.
NOTE: For dimming connections, use Class 1 wiring methods
only.
http://lighting.cree.com/warranty
Document
LPN00708X0002A0_A
Created By:
TMT
EMERGENCY DRIVER CHECK
NOTE: For short-term testing of the emergency function, the battery
must be charged for at least one hour. The emergency driver must be
charged for at least 24 hours before conduction a long-term test.
1.
When AC power is applied, the charging indicator light is
illuminated, indicating the battery is being charged. When power
fails, the emergency driver automatically switches to emergency
power, operating the LED array. When AC power is restored, the
emergency driver returns to the charging mode.
2.
Although no routine maintenance is required to keep the
emergency driver functional, it should be checked periodically to
ensure that it is working. The following schedule is recommended:
• Visually inspect the charging indicator light monthly. It
should be illuminated.
• Test the emergency operation of the fixture at 30-day
intervals for a minimum of 30 seconds. When the test
switch is depressed, the LED array should operate.
• Conduct a 90-minute discharge test once a year. The LED
array should operate for at least 90 minutes.
If the luminaire fails any of these checks, consult service personnel.
REFER ANY SERVICING INDICATED BY THESE CHECKS TO
QUALIFIED PERSONNEL. EMERGENCY DRIVER AND AC DRIVER
MUST BE FED FROM THE SAME BRANCH CIRCUIT.
|