C-LITE C-CP-C-SQ Serie Instructions D'installation

Publicité

Les langues disponibles

Les langues disponibles

INSTALLATION INSTRUCTIONS
C-CP-C-SQ Series
CAUTIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety
precautions should always be followed including the
READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
1.
DANGER- Risk of shock- Disconnect power before
installation.
DANGER – Risque de choc – Couper l'alimentation
avant l'installation.
2.
This luminaire must be installed in accordance with the
NEC or your local electrical code. If you are not familiar
with these codes and requirements, consult a qualified
electrician.
Ce produit doit être installé conformément à NEC ou votre
code électrique local. Si vous n'êtes pas familier avec ces
codes et ces exigences, veuillez contacter un électricien
qualifié.
3.
Suitable for wet locations.
Convient aux emplacements mouilles.
4.
Covered ceiling mount only.
Installation sur plafond couvert seulement.
5.
MIN. 75C SUPPLY CONDUCTORS.
LES FILS D'ALIMENTATION 75C MIN.
6.
Make certain power is OFF before starting installation or
attempting any maintenance.
7.
Do not recess the fixture.
8.
For supply wire temperature rating, refer to fixture label.
SAVE THESE INSTRUCTIONS
FOR FUTURE REFERENCE
DO NOT TOUCH THE LEDs OR WIRES COMING
FROM CIRCUIT BOARD DURING THE INSTALLATION
PROCESS. DAMAGE MAY OCCUR.
following:
http://lighting.cree.com/warranty
Document:
LPN00473X0001A2_B
Created By:
TMT
MOUNTING USING ¾" PLUG IN THE BACK
1.
Remove the four screws attaching the lens diffuser to the fixture
and set the screws and lens aside.
2.
Remove the screws attaching the reflector to the housing and set
aside.
3.
Remove ¾" plug from back for wiring access.
4.
Fixture is best mounted by drilling holes in the four corners of the
housing. Holes should be drilled from the outside of the casting
through the centers of each of the (4) circular ribbed mounting
supports in the corners of the housing. Make sure metal chips are
cleaned from inside housing after drilling. Fixture is to be secured
to the mounting surface using mounting hardware (supplied
by others) appropriate for the mounting surface. A high grade
caulking material, such as silicone rubber, should be used around
all the holes to ensure a watertight enclosure.
NOTE: Fixture can also be pendant mounted by threading the
customer supplied pendant into the ¾" mounting hole on the top
of the fixture. If using center conduit hole for pendant the wireway
MUST be filled with a high grade of silicone supplied by customer
to prevent water from entering fixture through the pendant. In
addition, Teflon tape should be used on conduit threads.
5.
Route the incoming power and ground leads through the hole
located in the center of the back of the fixture and through the
opening on the side of the LED mounting pad.
6.
Complete the wiring to the incoming power and ground (refer to
"Fixture Wiring" section).
7.
Replace the reflector and lens diffuser. Note: Make sure no wires
are pinched when replacing parts. Do not overtighten lens screws
to prevent damage to lens.
MOUNTING USING ½" PLUGS ON THE SIDE
1.
Remove the four screws attaching the lens diffuser to the fixture
and set the screws and lens aside.
2.
Remove the screws attaching the reflector to the housing and set
aside.
3.
Remove 1/2" plug from direction you intend to feed conduit. Teflon
tape should be used on conduit threads to prevent water entry.
NOTE: The (2) screws on either side of the 1/2" plug should not
be removed during installation. See Figure 1.
4.
Fixture is best mounted by drilling holes in the four corners of the
housing. Holes should be drilled from the outside of the casting
through the centers of each of the (4) circular ribbed mounting
supports in the corners of the housing. Make sure metal chips are
cleaned from inside housing after drilling. Fixture is to be secured
to the mounting surface using mounting hardware (supplied
by others) appropriate for the mounting surface. A high grade
caulking material, such as silicone rubber, should be used around
all the holes to ensure a watertight enclosure.
5.
Complete the wiring to the incoming power and ground (refer to
"Fixture Wiring" section).
6.
Replace the reflector and lens diffuser. Note: Make sure no wires
are pinched when replacing parts. Do not overtighten lens screws
to prevent damage to lens.
FIGURE 1
Do NOT Remove These Screws During
Installation
|
1-800-236-6800
Date:
4-25-2022

Publicité

Table des Matières
loading

Sommaire des Matières pour C-LITE C-CP-C-SQ Serie

  • Page 1 Document: LPN00473X0001A2_B Date: 4-25-2022 INSTALLATION INSTRUCTIONS Created By: C-CP-C-SQ Series MOUNTING USING ¾" PLUG IN THE BACK Remove the four screws attaching the lens diffuser to the fixture and set the screws and lens aside. Remove the screws attaching the reflector to the housing and set aside.
  • Page 2: Electrical Connections

    Document: LPN00473X0001A2_B Date: 4-25-2022 INSTALLATION INSTRUCTIONS Created By: C-CP-C-SQ Series ELECTRICAL CONNECTIONS FCC NOTICE Fixture is equipped with universal volt driver 120-277V (ie. 120V, 208V, 240V or 277V) CAUTION: Changes or modifications not expressly approved could void your authority to use this equipment. PHASE TO NEUTRAL WIRING 120/277V 1.
  • Page 3 Documento: LPN00473X0001A2_B Fecha: 4-25-2022 INSTRUCCIONES DE INSTALACIÓN Creado por: Serie C-CP-C-SQ MONTAJE USANDO EL TAPÓN DE 3/4” EN LA PARTE POSTERIOR Retire los cuatro tornillos que sujetan el difusor del lente a la luminaria y ponga a un lado los tornillos y el lente. Retire los tornillos que sujetan el refl...
  • Page 4: Conexiones Eléctricas

    Documento: LPN00473X0001A2_B Fecha: 4-25-2022 INSTRUCCIONES DE INSTALACIÓN Creado por: Serie C-CP-C-SQ CONEXIONES ELÉCTRICAS AVISO DE LA FCC El dispositivo está equipado con un controlador universal de voltaje de 120-277 V PRECAUCIÓN: Los cambios o modificaciones que no se autoricen (es decir 120 V, 208 V, 240 V o 277 V) expresamente podrían invalidar la garantía del equipo.
  • Page 5: Mesures De Sécurité Importantes

    Document : LPN00473X0001A2_B Date : 4-25-2022 INSTRUCTIONS D’INSTALLATION Créé par : Série C-CP-C-SQ MONTAGE À L’AIDE D’UNE DOUILLE DE 13 MM (1/2 PO) À L’ARRIÈRE Retirez les quatre vis fi xant le diffuseur à lentille au luminaire et placez les vis et la lentille de côté. Retirez les vis qui fi...
  • Page 6: Raccordements Électriques

    Document : LPN00473X0001A2_B Date : 4-25-2022 INSTRUCTIONS D’INSTALLATION Créé par : Série C-CP-C-SQ RACCORDEMENTS ÉLECTRIQUES AVIS DE LA FCC Le luminaire est équipé d’un système d’entraînement de tension universelle de 120 à 277 V MISE EN GARDE : Les changements ou modifications non expres- (c’est-à-dire, 120 V, 208 V, 240 V ou 277 V).

Table des Matières