(4) Wall and ceiling side opening position
Figure shows view from front.
ø100 wall side
90
opening (for left-
side drain hose)
Figure shows view from top.
Wall
ø100 ceiling
opening
125
ø100 ceiling
opening
* If the optional drain up kit is installed, create a ø100 hole
along the dotted line (part marked with * in fi gure).
3-2. Suspending the Indoor Unit
(1) Place the full-scale diagram (supplied) on the ceiling at the
location where you want to install the indoor unit. Use a
pencil to mark the drill holes (Fig. 3-5).
Full-scale installation
diagram
NOTE
Since the diagram is made of paper, it may shrink or stretch
slightly because of high temperature or humidity. For this
reason, before drilling the holes maintain the correct dimensions
between the markings.
(2) Drill holes at the 4 points indicated on the full-scale
diagram.
(3) Depending on the ceiling type:
a) Insert suspension bolts (Fig. 3-6).
or
b) Use existing ceiling supports or construct a suitable
support (Fig. 3-7).
Hole-in-anchor
Hole-in-plug
Suspension bolt (M10 or 3/8")
(field supply)
A
PAC-i̲T1-type.indb 8
PAC-i̲T1-type.indb 8
All manuals and user guides at all-guides.com
Ceiling
ø100 wall
side opening
135
*
Unit: mm
Fig. 3-4
Ceiling
Wall
Fig. 3-5
Insert
Concrete
Fig. 3-6
Ceiling tiles
Ceiling support
A
Fig. 3-7
WARNING
It is important that you use extreme care in supporting
the indoor unit from the ceiling. Ensure that the ceiling is
strong enough to support the weight of the unit. Before
hanging the ceiling unit, test the strength of each attached
suspension bolt.
(4) Screw in the suspension bolts, allowing them to protrude
from the ceiling (Figs. 3-6 and 3-7). The distance of each
exposed bolt must be of equal length within 50 mm.
(Fig. 3-8)
Unit
Ceiling
surface
Fixture
(5) Before suspending the indoor unit, remove the 2 or 3
screws on the latch of the air-intake grilles, open the
grilles, and remove them by pushing the claws of the
hinges (Fig. 3-9). Then remove both side panels sliding
them along the unit toward the front after removing the 2
attachment screws. (Fig. 3-10)
Pull out the air-intake grille
pushing claws of the hinges
Screw
Latch
Slide
Air-intake grille
Slide toward
front side
Side panel
(6) Carry out the preparation for suspending the indoor unit.
The suspension method varies depending on whether
there is a suspended ceiling or not. (Figs. 3-11 and 3-12)
(7) Suspend the indoor unit as follows:
a) Mount 1 washer and 2 hexagonal nuts on each
suspension bolt (Fig. 3-13).
Unit
Fixture
8
Fig. 3-8
Hinge
Fig. 3-9
Fig. 3-10
Suspension bolt
(field supply)
Ceiling surface
Washer (supplied)
Double nut
(field supply)
Fig. 3-11