EN
2-3. Electrical Performance
2-3-1. ECB2500 Specification
MODEL
Rating Power
Peak Power (3Sec.)
Surge Power (<0.2Sec.) 4000W
Waveform
Efficiency (Max.)
Output Voltage
(@rated VDC)
Output Frequency
Total Harmonic
Distortion (THD)
DC Voltage
Voltage Range
No load Power
Consumption
On Mode @ Save Mode
On Mode @ No Load Mode
Fuse
AC Range
Frequency Selectable
Synchronous
Frequency
Circuit Breaker
①
Transfer Switch
BAT.Low Alarm ± 3%
BAT.Low Shut-down ± 3%
BAT.Low Restart ± 3%
BAT.High Alarm ± 3%
BAT.High Shut-down ± 3%
BAT.High Restart ± 3%
Input Protection
Output Protection
6
All manuals and user guides at all-guides.com
ECB25-112
ECB25-124 ECB25-148
2500W (de-rating after 40°C, refer to de-rating curve)
3000W
Pure Sine Wave
88%
89%
100 / 110 / 115 / 120VAC ± 3%
50 / 60Hz ± 0.1%
< 3% @ under condition:
greater than 1.15 times of the rated VDC,
110V / linear load)
12VDC
24VDC
10.0~16.0 VDC 20.0~32.0 VDC 40.0~64.0 VDC 10.0~16.0 VDC 20.0~32.0 VDC 40.0~64.0 VDC
@12VDC
@24VDC
0.9A
0.35A
< 2.9A
< 1.4A
40Ax9
20Ax9
100 / 110 / 115 / 120VAC ± 12.5%
50 / 60 Hz
47~57 / 53~63 Hz
35A
Standard ATS:Inverter to utility AC:8~10ms.; Utility AC to inverter:16~50ms.
Optional STS module:Single < 4ms; N+1 & 1P3W & 3P4W < 6ms
Protection
10.5VDC
21.0VDC
10.0VDC
20.0VDC
12.5VDC
25.0VDC
15.5VDC
31.0VDC
16.0VDC
32.0VDC
15.0VDC
30.0VDC
Reverse Polarity (Fuse) / Under Voltage / Over Voltage Protection / AC over current (Breaker)
Short Circuit / Overload / Over Temperature / Over Voltage Protection
ECB25-212 ECB25-224
Output
90%
88%
200 / 220 / 230 / 240VAC ± 3%
< 3% @ under condition:
greater than 1.15 times of the rated VDC,
230V / linear load)
DC Input
48VDC
12VDC
@48VDC
@12VDC
0.3A
1.1A
< 0.8A
< 3.6A
15Ax6
40Ax9
AC Input
200 / 220 / 230 / 240VAC ± 12.5%
42.0VDC
10.5VDC
40.0VDC
10.0VDC
50.0VDC
12.5VDC
62.0VDC
15.5VDC
64.0VDC
16.0VDC
60.0VDC
15.0VDC
ECB25-248
88%
90%
24VDC
48VDC
@24VDC
@48VDC
0.7A
0.4A
< 1.8A
< 1A
20Ax9
15Ax6
20A
21.0VDC
42.0VDC
20.0VDC
40.0VDC
25.0VDC
50.0VDC
31.0VDC
62.0VDC
32.0VDC
64.0VDC
30.0VDC