1. Select the Setup Menus with the help of Function Codes:
Format:FUNC <Function Code>
After "Enter", the Setup Menu for the Function Code will be called.
The <Function Code>= 0~18
2. Command to query the Functions No:
Format:FUNC?
After "Enter", the unit's "Function Code" appears on the PC screen.
3. Command to query the set value of the Function:
Format:SETT?
After "Enter", the existing set value of the function appears on the PC
screen.
4. Command to set or adjust the value of the Function:
Format:SETT <value>
After "Enter", the new value of the Function is set Choose the <value> of the
function.
6-1-4. Setting interface
1. OVP Setting <FUNC0>:Set the Over Voltage Protection (OVP) and
shutdown.
Default = 16 VDC @ 12V Model, 32 VDC @ 24V Model, 64 VDC @ 48V
Model
Model
2. OVP Recovery <FUNC1>:When the DC input voltage is higher than the OVP
setting, the ECB-series shuts-down; once the input voltage falls below the
set OVP value, the ECB-series will automatically restart.
Default = 15 VDC @ 12V Model, 30 VDC @ 24V Model, 60 VDC @ 48V
Model
Model
38
All manuals and user guides at all-guides.com
O/P Voltage
RS-232 Baud rate
O/P Frequency
Sync Frequency
Overload Alarm
Table 28. Command for accessing setup menus and adjusting values
Setting value range
12 V
15 VDC ~ 16 VDC
24 V
30 VDC ~ 32 VDC
48 V
60 VDC ~ 64 VDC
Table 29. OVP Setting <FUNC0>
Setting value range
12 V
13 VDC ~ 15 VDC
FUNC15
LCD Auto-off
FUNC16
Buzzer Setting
FUNC17
Alert Setting
FUNC18
Language