6. O/P Voltage <FUNC5>:Setting the ECB-series output voltage on the inverter
operation.
Default = 110 VAC @ 110 V Model, 230 VAC @ 230 V Model
Model
110 V
230 V
7. RS-232 Baud rate <FUNC6>:
Default setting:4800
Setting Menu
RS-232
Baud rate
8. O/P Frequency <FUNC7>:Setting the ECB-series output frequency on the
inverter operation.
Default = 60 Hz @ 110 V Model, 50 Hz @ 230 V Model.
Model
110 V
230 V
9. Sync Frequency <FUNC8>:If a generator is distorted. The output waveform
(too low frequency) is used as AC source, the allowed frequency window for
the incoming AC power can be enlarged.
Example1:
AC input = 230 VAC / 50Hz, User setting Value= 7Hz
When the ECB-series "Output frequency" is within The Range of 43 Hz~57
Hz, the internal transfer relay will close. When the output frequency is less
than 43 Hz or more than 57 Hz, the internal transfer relay will still open.
40
All manuals and user guides at all-guides.com
Note
The value of the voltage set for the "UV Alarm" should be equal to or
higher than the value set for "UVP" or else the unit will shut-down
without any audible warning.
Setting value range
97 VAC ~ 123 VAC
194 VAC ~ 246 VAC
Table 34. O/P Voltage <FUNC5>
SETT<value>
0
1
2
3
4
Table 35. RS-232 Baud rate <FUNC6>
Setting value range
47 Hz ~ 63 Hz
47 Hz ~ 63 Hz
Table 36. O/P Frequency <FUNC7>
1200
2400
4800
9600
19200