the saving mode.
B. Power device leaving saving mode(re-start)
Restart threshold = rate power x setting % x 2~3
In case the power over the restart threshold, the power device will re-start and
provide the AC power.
S1
S2
S3
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
1=ON / 0=OFF
3-3-3. S4~S6 Set-up for parallel application
S1
S2
S3
X
X
X
X
X
X
X
X
X
X
X
X
1=ON / 0=OFF
3-3-4. Parameter select: "S8" select ECB's parameter setting by dip switch or LCM
Set Value
LCM
DIP switch
1=ON / 0=OFF
14
All manuals and user guides at all-guides.com
S4
S5
S6
X
0
0
0
X
1
0
0
X
0
1
0
X
1
1
0
X
0
0
1
X
1
0
1
X
0
1
1
X
1
1
1
Table 7. Power saving mode set-up
S4
S5
S6
X
0
0
0
X
0
0
1
X
0
1
1
X
1
0
0
X
1
0
1
X
1
1
1
Table 8. Parallel application set-up
S8
0
1
S7
S8
0
X
Power saving DISABLE
Go in power saving mode when output load is
0
X
under 2% of rating power
Go in power saving mode when output load is
0
X
under 3% of rating power
Go in power saving mode when output load is
0
X
under 4% of rating power
Go in power saving mode when output load is
0
X
under 5% of rating power
Go in power saving mode when output load is
0
X
under 6% of rating power
Go in power saving mode when output load is
0
X
under 7% of rating power
Go in power saving mode when output load is
0
X
under 8% of rating power
S7
S8
Master (0°); "R" Phase
to be used for 1Ø3W output in series
1
X
connection(Master) or 3Ø4W output
connection("R" Phase)
Slave (0°) with current sharing
1
X
to be used in parallel connection only
Slave (180°), to be used for 1Ø3W output in
1
X
series connection(L-NN-L)
Slave (-120°), "S" Phase
1
X
to support "S" Phase be(-120°) in 3Ø4W
output connection
Slave (120°), "T" Phase
1
X
to support "T" Phase be(120°) in 3Ø4W
output connection
1
X
Disable parallel function
Scenario
Scenario