If the AC Load is 3 times higher than Saving Level, inverter will recover and
output normally to AC Load.
14. Bypass Relay <FUNC13>:The setup is provided in one of the following two
ways.
On-line Mode or Off-line Mode ( Exacting, Normal, Haphazard).
Default = Normal (Off line).
Model
Haphazard
Normal
Exacting
On-line
42
All manuals and user guides at all-guides.com
SETT <value>
The transfer relay will switch "ON" or "OFF".
0
Conformance to, phase and frequency
synchronization will not be considered.
The transfer relay will be "ON" if AC input (Grid)
power is available. The DC-AC inverter will remain
synchronized and Phase with the incoming AC power
1
(Grid). The relay will NOT switch off if the grid
frequency is beyond the range set under Sync
Frequency window.
The transfer relay will switch "ON" or "OFF" based on
2
conformance to, the Phase and Sync Frequency.
Always supplied by battery until which has run down
3
(UVP) then switch to grid.
Table 39. Bypass Relay <FUNC13>
Figure 34. Frequency and phase synchronous
Transfer Relay
Switching Feature