Télécharger Imprimer la page

Panasonic S C09 3E8 Serie Mode D'emploi page 17

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 224
Optional cables:
3-way valve cable
2-way valve cable
Booster heater cable
Extra pump cable
Boiler contact cable
Optional cables:
Pump zone 1 cable
Pump zone 2 cable
Solar pump cable
Pool pump cable
Room thermostat zone 1 cable
Room thermostat zone 2 cable
Mixing valve zone 1 cable
Mixing valve zone 2 cable
Optional cables:
External control cable
Tank sensor cable
Outdoor air sensor cable
Tank OLP cable
Remote controller cable
Room sensor zone 1 cable
Room sensor zone 2 cable
Buffer tank sensor cable
Pool sensor cable
Water sensor zone 1 cable
Water sensor zone 2 cable
Demand signal cable
Solar sensor cable
SG signal cable
Heat/Cool switch cable
External Compressor switch cable
Terminal screw on PCB
M3
M4
Connecting Cables Length
When connecting cables between Indoor Unit and external devices,
the length of the said cables must not exceed the maximum length
as shown in the table.
External device
Two-way valve
Three-way valve
Mixing valve
Room thermostat
Booster heater
Extra pump
Solar pump
Pool pump
Pump
Boiler contact
External control
Tank sensor
Room sensor
Outdoor air sensor
Tank OLP
Buffer tank sensor
Pool water sensor
Solar sensor
Water sensor
Demand signal
SG signal
Heat/Cool switch
External compressor switch
ACXF60-03130_EN ES IT.indb 17
ACXF60-03130_EN ES IT.indb 17
Power Supply 1 cord
Power Supply 2 cord
Indoor Unit/Outdoor
Unit Connecting cable
from optional
PCB
from optional PCB
Maximum tightening torque cN•m {kgf•cm}
50 {5.1}
120 {12.24}
Maximum cables length (m)
50
50
50
50
50
50
50
50
50
50
50
30
30
30
30
30
30
30
30
50
50
50
50
Connection of the main PCB
C O N C O N
2-way
3-way
valve
valve
  Signal inputs
L N =AC230V, Heat, Cool=Thermostat heat, Cool
terminal
Optional Thermostat
It does not function when using the optional
PCB
Dry contact Vcc-Bit1, Vcc-Bit2 open/short
OLP for booster
(System setup necessary)
heater
It is connected to the safety device (OLP) of
DHW tank.
Dry contact Open=not operate, Short=operate
(System setup necessary)
External control
Able to turn ON/OFF the operation by external
switch
Connected (Please use 2 cores wire for relocation
Remote controller
and extension. Total cable length shall be 50m
or less.)
  Outputs
AC230V N=Neutral Open, Close=direction (For
3-way valve
circuit switching when connected to DHW tank)
AC230V N=Neutral Open, Close (Prevent water
2-way valve
circuit pass through during cooling mode)
AC230V (Used when indoor unit pump capacity is
Extra pump
insuffi cient)
AC230V (Used when using booster heater in DHW
Booster heater
tank)
Boiler contact
Dry contact (System setup necessary)
  Thermistor inputs
Zone 1 room
PAW-A2W-TSRT
sensor
the optional PCB
Outdoor air
AW-A2W-TSOD (Total cable length shall be 30m
sensor
or less)
Tank sensor
Please use Panasonic specifi ed part
Connection of Optional PCB (CZ-NS4P)
Optional
Optional
Thermostat 2
Thermostat 1
L
N Cool Heat L
N Cool Heat
Pool
Pump
Solar
Pump
Error
signal
Zone 1
Pump
Zone 2
Pump
Zone 2
Zone 1
Buffer
Pool
room
room
Tank
water
sensor
sensor
sensor
sensor
OLP for booster
heater
Zone 1 room sensor
Outdoor air sensor
Tank sensor
External control
Remote controller
Boiler contact
Extra pump
Booster heater
H C N L
Optional
Thermostat 1
It does not work when using
Mixing
Mixing
valve 1
valve 2
N
O
C
N
O
C
Ext.
comp.
SW
Heat/
Cool
SW
Vcc
SG
Bit1
signal
Bit2
Zone 2
Zone 1
Demand
Solar
sensor
water
water
signal
sensor
sensor
9/22/2016 4:21:32 PM
9/22/2016 4:21:32 PM
17

Publicité

loading

Ce manuel est également adapté pour:

S c12 9e8 serieS c16 9e8 serie