Quick Start Parameters
Notes:
•
P000 locks the unit, The unlocking value is 1954. All other values lock the unit.
•
Defaults are shown with an *
P001 Operation: Sets the type of
measurement required for the application.
Standard Mode Dual Point Mode
Primary
Index
Global
0
Out-of-service
1
Material Level
2
Space
3 * Distance (transducer to material)
Values
4
DPD – dual point difference
5
DPA – dual point average
6
OCM – open channel flow rate
7
Pump Totalizer
P002: Material: Measures material type.
Liquid, may involve solids.
Standard Mode
Primary
Index
Global
1 * Liquid or horizontal solid surface
Values
2
Solid or angled surface
P003 Maximum Process Speed:
Determines level change reaction.
Primary
Transducer
Index
1
Slow (0.1 m/min)
Values
2 * Medium (1 m/min)
3
Fast (10 m/min)
P004 Transducer: Specifies transducer.
Primary
Standard Mode Dual Point Mode
Index
Global
No transducer attached (preset for
0
*
Dual Point)
1
ST-25
2
ST-50
100
STH
101
XCT-8
Values
XPS-10 (preset for Standard
102
*
Mode)
103
XCT-12
104
XPS-15
112
XRS-5
250
mA input
Page EN-8
Transducer
Dual Point Mode
Transducer
Transducer
MultiRanger – QUICK START MANUAL
P005 Units: Specifies units used for
dimensional values.
Primary
Global
Index
1 * Meters
2
Centimeters
Values
3
Millimeters
4
Feet
5
Inches
P006 Empty: Distance in Units (P005) from
transducer face to process empty point.
Primary
Transducer
Index
Range: 0.000 to 9999
Values
Preset: 5.000m (or equivalent
depending on units)
Alters
•
P007 Span
Altered By •
P005 Units
P007 Span: Sets range levels to be
measured.
Primary
Level
Index
Range: 0.000 to 9999
Values
Preset: based on Empty (P006)
Note: Please refer to the Instruction
Manual to set up inputs, alarms and
controls, communications, and other
functionality.