SWIMMING POOL HEAT PUMP TYPE PV

4.3 PARAMETER LIST AND BREAKDOWN TABLE

(1) Electronic control fault table
Can be judged according to the remote controller failure code and troubleshooting
Fault
Protect/fault
Reason
display
Standby
Non
Normal boot
Non
Inlet Temp.
P01
The temp. Sensor is broken or short circuit Check or change the temp. Sensor
Sensor Fault
Outlet Temp.
P02
The temp. Sensor is broken or short circuit Check or change the temp. Sensor
Sensor Fault
Ambient Temp.
P04
The temp. Sensor is broken or short circuit Check or change the temp. Sensor
Sensor Fault
Coil Temp.
P05
The temp. Sensor is broken or short circuit Check or change the temp. Sensor
Sensor Fault
Suction Temp.
P07
The temp. Sensor is broken or short circuit Check or change the temp. Sensor
Sensor Fault
Discharge Temp.
P081
The temp. Sensor is broken or short circuit Check or change the temp. Sensor
Sensor Fault
High Pressure
E01
The high-pressure switch is broken
Prot.
Low Pressure
E02
Low pressure1 protection
Prot.
Flow Switch
No water/little water in water
E03
Prot.
system
Anti-freezing
E07
Water flow is not enough
Prot.
Primary Anti-freezing
E19
The ambient temp. Is low
Prot.
Secondary Anti-
E29
The ambient temp. Is low
freezing Prot.
Inlet and outlet
Water flow is not enough
E06
temp. too big
and low differential pressure
Low temperature
Non
The environment temp. is low
protection
Comp.
E051
The compressor is overload
Overcurrent Prot.
Exhaust Air over
P082
The compressor is overload
Temp Prot.
Communication
Communication failure between
E08
Fault
wire controller and mainboard
Antifreeze Temp.
antifreeze temp sensor is broken or
P09
Sensor Fault
short circuited
Waterway
water temp. or ambient temp. is
E05
Anti-freezing Prot.
too low
EC fan feedback
There is something wrong with fan
F051
Fault
motor and fan motor stops running
Pressure sensor
PP
The pressure Sensor is broken
Fault
1. Motor is in locked-rotor state 2.The wire
Fan Motor1
F031
connection between DC-fan motor
Fault
module and fan motor is in bad contact
1. Motor is in locked-rotor state 2.The wire
Fan Motor2
F032
connection between DC-fan motor
Fault
module and fan motor is in bad contact
Communication Fault
Speed control module and main board
(speed
E081
communication fail
control module)
20
WWW.NORSUP.EU
Elimination methods
Check the pressure switch and cold
circuit
Check the pressure switch and cold
circuit
Check the pipe water flow and
water pump
Check the pipe water flow and whether
water system is jammed or not
Check the pipe water flow and whether
water system is jammed or not
Check whether the system of the
compressor running normally
Check whether the system of the
compressor running normally
Check the wire connection between
remote wire controller and main board
check and replace this temp sensor
Check whether fan motor is broken
or locked or not
Check or change the pressure
Sensor or pressure
1. Change a new fan motor
2. Check the wire connection and make
sure they are in good contact
1. Change a new fan motor
2. Check the wire connection and make
sure they are in good contact
Check the communication connection
Alterations which serve the technological progress as well as errors excepted!
SWIMMING POOL HEAT PUMP TYPE PV
FREQUENCY CONVERSION BOARD FAULT TABLE:
Fault
Protection/fault
Reason
display
Drv1 MOP alarm
F01
MOP drive alarm
Frequency conversion board and main
Inverter offline
F02
board communication failure
IPM protection
F03
IPM modular protection
Lack of phase, step or drive hardware
Comp. Driver Failure
F04
damage
Motor current feedback open circuit or
DC Fan Fault
F05
short circuit
IPM Overcurrent
F06
IPM Input current is large
DC bus voltage>Dc bus over-voltage
Inv. DC Overvoltage
F07
protection value
DC bus voltage<Dc bus over-voltage
Inv. DC Less voltage
F08
protection value
The input voltage is low, causing the input
Inv. Input Less voltage F09
current is high
The input voltage is too high, more than
Inv. Input Overvolt.
F10
outage protection current RMS
Inv. Sampling Volt.
F11
The input voltage sampling fault
Comm. Err DSP-PFC
F12
DSP and PFC connect fault
Input Over Cur.
F26
The equipment load is too large
PFC fault
F27
The PFC circuit protection
IPM Over heating
F15
The IPM module is overheat
Compressor magnetic force is
Weak Magnetic Warn F16
not enough
Inv. Input Out Phase
F17
The input voltage lost phase
IPM Sampling Cur.
F18
IPM sampling electricity is fault
Inv. Temp. Probe Fail
F19
Sensor is short circuit or open circuit
Inverter Overheating
F20
The transducer is overheat
Inv. Overheating Warn F22
Transducer temperature is too high
Comp. Over Cur. Warn F23
Compressor electricity is large
Input Over Cur. Warn
F24
Input current is too large
EEPROM Error Warn
F25
MCU error
V15V over/
F28
The V15V is overload or undervoltage
undervoltage fault
(2) Parameter list
Meaning
Refrigeration target temperature set point
Heating the target temperature set point
Automatic target temperature set point
Alterations which serve the technological progress as well as errors excepted!
Elimination methods
Recovery after the 150s
Check the communication connection
Recovery after the 150s
Check the measuring voltage Check
frequency conversion board hardware
Check whether current return wires
connected motor
Check and adjust the current measurement
Check the input voltage measurement
Check the input voltage measurement
Check the input voltage measurement
Check the input voltage measurement
Check and adjust the current measurement
Check the communication connection
Check the PFC switch tube short circuit or not
Check and adjust the current measurement
Check and measure the voltage adjustment
Check and adjust the current measurement
Inspect and replace the sensor
Check and adjust the current measurement
Check and adjust the current measurement
The compressor over-current protection
Check and adjust the current measurement
Check whether the chip is damaged
Replace the chip
Check the V15V input voltage in range
13.5v~16.5v or not
Default
Remarks
28°C
Adjustable
28°C
Adjustable
27°C
Adjustable
ORIGINAL MANUAL NORSUP
EN
DE
EN
NL
DE
FR
DK
SE
21