The output power and the charging currents are displayed on the Remote Control.
In the Remote Control there is an additional Alarm Contact and a built-in Control
Input. These two functions are available through Tip-jack RJ11/4 for use. This
Auxiliary Contact is Front / Work Contact (max. 0.5A!), which is independent from the
Auxiliary
Contact
of
the
COMPACT. This con-tact is
active in case of an alarm of
the COMPACT.
The Control Input is connected
in parallel to the ON/OFF-
push button. The COMPACT
can be switched on or off
through this input with an
impulse button or an impulse
contact.
Caution: No external voltage
should be connected to this
Input Control.
Order Number for Remote Control: RCC-01
Dimensions: H x B x T / 111.5 x 136.5 x 25mm

4.11 The Temperature sensor CT-35

Operating voltage of lead-acid batteries change depends
on the temperature. To correct the operating voltages
according to the actual temperatures, a temperature
sensor can be connected to the COMPACT.
The compensation through the sensor is –3mV/°C/Cell.
Order Number: CT-35
Dimensions: H x B x T / 58 x 51.5 x 22mm
4.12 Remote control for „Power Sharing" RPS-01
If the Remote control RPS-01 is installed, the
Trimmer (26) "INPUT LIMIT" has to be set on
the value max.. The COMPACT takes into
account the lowest values set on the inverter
and on the Remote control.
The current available at the COMPACT input
will be determined by the power of the
connected source (generator, grid etc...). The
potentiometer on the RPS-01 must be
adjusted lower or equal to max. value of the
power source.
For instance if the source is a generator of
2000 Watt, the potentiometer has to be set at
max. 8A. This value is obtained in dividing
2000 Watt by 230V. If the COMPACT is connected to a power source which is
protected by a 6A circuit breaker, the potentiometer must be set at a max. value of
6A.