Installation and Operating Instructions
EN
m
WARNING
m
WARNING
m
WARNING
m
m
WARNING
m
ATTENTION
Central ventilation unit – KWL 500 W/W ET
The arrangement of the air filters can be found on the unit label. When installing the filter, the air direction according to
the unit label must be observed, which is indicated by arrows on the filters.
Proceed as follows to replace the filters:
1. Open both upper snap-in hooks on the unit door and
remove the unit door.
2. Pull intake air filter
and extract air filter
ò
and replace (see Fig. 38).
3. Confirm the filter replacement:
– enter the filter replacement date and confirm via the
easyControls 3.0 software in the menu "Home-
page"> "Filter replacement".
m
– confirm with
via the control element KWL-BE
Touch.
– the filter replacement can be confirmed via the slide
switch control element KWL-BE Eco. For this purpo-
se, switch through all operating stages 4x within one
second (up–down–up–down.
The unit is equipped with filters ISO Coarse 65 % on the intake air and extract air sides as standard.
The filters are available as accessories:
Replacement air filter Coarse filter Coarse 65 % (2 pcs.) ELF-KWL 500/4/4
Replacement air filter Fine filter ePM 1 50 % (1 pc.)
Replacement air filter Activ. carbon ePM 2.5 60 % (1 pc.) ELF-KWL 500 AK
The filters can be ordered at www.Ersatzluftfilter.de
9.3
Heat exchanger maintenance and cleaning
9.3.1 Heat exchanger maintenance
The heat exchanger must be checked for contamination and dirt (visual inspection) and, if necessary, cleaned, see
chapter 9.3.2 „Heat exchanger cleaning", page 29.
9.3.2 Heat exchanger cleaning
m
Risk of burns due to hot surfaces!
Hot surfaces can cause serious burns.
> Allow unit to cool down for at least 5 minutes or wait until the fans are turned off.
m
Risk of injury due to rotating fans!
Rotating fans can injure limbs and cause serious injuries.
> Before working on the unit, wait until the fans are turned off.
m
Risk of injury due to the unit door falling down!
The unit door can fall down when removing and cause serious injuries.
> Wear protective footwear.
> Carefully remove the unit door with both hands.
1. Open both upper snap-in hooks on the unit door.
2. Remove the unit door.
m
Risk of injury due to the high weight of the heat exchanger!
The heat exchanger can fall down and cause serious injuries when removed from the unit.
> Wear protective footwear.
> Carefully remove the heat exchanger from the unit with both hands.
3. Remove terminal strip
ò
4. Carefully remove the heat exchanger
Damage to the heat exchanger due to the use of aggressive cleaning agents.
Aggressive cleaning agents can damage the heat exchanger.
> Do not use aggressive cleaning agents.
to the front
ù
ELF-KWL 500/7
at top of heat exchanger (see Fig. 39).
ù
from the unit (see Fig. 40).
Fig. 39
ò
29
Fig. 38
ù
ò
ò
Ref. no. 00039
Ref. no. 00042
Ref. no. 04199
Fig. 40
ù