Parameter's precision
Parameters
Position on
menu
structure
Sensor
Installation >
Calibration
Sensor
Sensor
Installation >
Regulation
Regulation
Regulation
Installation >
Type
Regulation
Smart Start
Installation >
Regulation
Table 9
40
Description
The calibration must be done after one day of
working with the same setting temperature in
accordance with the following description:
▶ Put a thermometer in the room at 1,5 m
distance from the floor and check the real
temperature in the room after one hour.
▶ Then, select the sensor you wish to calibrate.
▶ Use the (-) or (+) keys to enter the real value
Only the heating element driven by the
thermostat must be used during the complete
step of the calibration.
Calibration can be erased by using the RESET
function.
Air: only internal sensor is used, no floor
limitation
ON/OFF: regulation made by hysteresis +/-
0,3°C.
PID: use a PID regulation.
The function can be activated/deactivated: in
Program Menu, the positive steps will be
anticipated according to the current temperature
and the next step point.
C-IR 20 – 6721851970 (2023/10)