Used to enable/disable the remote control communication, only when DIP switch 7 is "OFF".
RC
When an activation signal (see RC/SET input jumper for settings) is applied to the RC input of the
(REMOTE
terminal block, Remote Control will be enabled.
CONTROL)
Note: DIP switch 7 "ON" constantly enables RC communication.
WARNING:
Turn DIP switch 7 "OFF" after installation and when leaving the site for security reasons. This
will prevent unauthorized use of a remote control unit that may be used to disable the
detector.
Not relevant in BUS mode
TERMINAL BLOCK 2
DESCRIPTION
AM/FAULT
Normally closed output
The AM/FAULT output opens in the following events:
Detector is masked (ALARM also opens in this case)
Self Test failed
Input voltage is low (6VDC-8VDC)
TAMPER
Normally closed output
ALARM
Normally closed output
Ind. LuNAR RK200DTG3 Installation Guide
27