All manuals and user guides at all-guides.com
Relay Mode Configuration (DIP
switch 6=OFF)
:
DIP switch
Description
1
Used to determine the operation of the ACT
DIP switch ON: ACT is enabled
DIP switch OFF: ACT is disabled (default factory)
2
Used to determine the operation of the detector's LEDs Dip switch ON: LEDs are
enabled (default factory)
DIP switch OFF: LEDs are disabled
3
Used to determine the operation of the "Green Line" (See Note below)
DIP switch ON: "Green Line" is enabled
DIP switch OFF: "Green Line" is disabled (default factory)
4
Used to determine the type of Self Test (See Note below) DIP switch ON: Local
Self Test:
In case the local self test fails, the FAULT/AM Relay is activated for a period of 2.5 secs. DIP
switch OFF: Remote Self Test (default factory):
In case the remote self test passes, the Alarm Relays are activated for a period of 5 secs.
In case the test fails, FAULT/AM Relay is activated for a period of 2.5 seconds.
5
Used to determine whether Active IR Anti-Masking is active. (See Note below)
DIP switch ON: Enable
DIP switch OFF: Disable (default factory)
IMPORTANT:
If the AM is enabled via DIP Switch 5, the cover must be fitted within 1 minute from applying the power.
If the detector is already powered up and DIP Switch 5 is turned on, the unit must be down powered to
reset the AM calibration.
6
Used to determine the detector's connection mode DIP switch OFF: Relay mode
Used to determine if the Remote Control communication is enabled or disabled.
Number
Green Self
RELAY REMOTE
ACT
LED AM
N/A
N/A Line
Test
MODE CONTROL
ON
1
2
3
4
5
6
7
Ind. LuNAR RK200DTG3 Installation Guide
8
9
23