MODBUS CONNECTION
EXcon HMI Touch is connected to the EXcon Master by means of a
Modbus cable. The Modbus cable can be connected to the EXcon
HMI Touch by means of the RJ12 6P4C port or four single-wire
screw terminals. Whether the RJ12 6P4C port or screw terminals
are used does not influence the available functions or operation.
Modbus RJ12 6P4C
Connect the Modbus cable to the Modbus port for a hand terminal
on the EXcon Master and to the RJ12 6P4C port on the EXcon
HMI Touch (see fig. 5).
Modbus screw terminals
Connect the Modbus cable to the Modbus port for a hand terminal
on the EXcon Master and to the corresponding screw terminals on
the EXcon HMI Touch (see fig. 6).
RJ12
Screw terminals
1
+24 V
2
GND (earth)
3
Bus "B"
4
Bus "A"
5
+24 V
6
GND (earth)
TECHNICAL DATA
Supply voltage ........................................................24 V DC +/-10%
Cable dimensions ............................................. 10 x max. 0.75 mm²
Relative humidity ...................................... 0-95% (non-condensing)
Operating temperature .....................................................-10/+40°C
Enclosure rating .......................................................IP21 (EN 60529)
Port ........................................................................... 1 x RJ12 6P4C
......................................................................... 10 x screw terminals
Dimensions ............................................. 80x121x42 mm (see fig. 2)
Installation depth ................................................................... 22 mm
Max. power consumption .................................................... 900 mW
Standby power consumption ............................................. 600 mW