Installation
Connecting the PDU
2-1
Each model is equipped with 1 of 2 different input plugs.
Model Name
Input Plug
PDUMV30HV2
L6-30P
IEC 309 32A
PDUMV32HV
BLUE (2P + E)
2-2
Connect the input plug to your facility's
compatible AC power source.
2-3
Connect your equipment's input plugs to
the appropriate outlets on the PDU.
Note: It is recommended that you do not
connect a live load to the PDU. If the load you
intend to connect has an ON/OFF switch, please
turn the switch to OFF prior to connection.
2-4
Optional Cord Retention Procedure
Use the included C14 and C20 plastic
sleeves to secure plugs to receptacles.
Attach the sleeve to the plug, making
sure that the pull tabs
the plug and that the fit is secure. To
unplug equipment properly, use the pull
tabs to remove the plug and sleeve from
the receptacle.
Max Input
Input
Amps (Limited by
Voltage
Input Cord and Plug)
Range
24A
200-240V
32A
200-240V
Bank 1
LINE L1-L2
remain outside
A
4
L6-30P
Output
Voltage
Range
Breakers
Length
2 x Double
200-240V
Pole, 20A
Branch-Rated
2 x Single Pole,
200-240V
20A Branch-
Rated
2-2
L1-
L2
2-3
A
2-4
N (Blue)
L [Φ] (Brown)
Ground
(Green/
Yellow)
IEC 309 32A
BLUE (2P + E)
Cord
Outlets
48 Total:
2 Banks of (4) C19
and (20) C13
10 ft.
(3 m)
48 Total:
2 Banks of (4) C19
and (20) C13
L6-30P