4.1.2 ADDING SECTIONS
Add chimney sections, according to the manufacturers installation instructions. The chimney must extend at
least, 3 feet (1m) above its point of contact with the roof and at least 2 feet (0.6m) higher than any wall, roof,
building or obstacle within 10 feet (3m) horizontally.
3 FT
(1m)
MIN
All manuals and user guides at all-guides.com
2 FT (0.6m) MIN
10 FT (3m)
TO NEAREST
ROOFLINE
10 FT (3m)
OR MORE
FLAT ROOF
LESS THAN
10 FEET
(3m)
2 FT (0.6m)
RIDGE
MIN
3 FT (1m)
3 FT (1m)
MIN
MIN
15
3 FT (1m)
MIN
LESS THAN
10 FEET
(3m)
2 FT (0.6m)
MIN
WALL
59.1B