Fault
Reason
Does not switch
No power
(green LED does not light up)
Nivotester defect
Contacts welded together
(after short-circuit)
Measuring transmitter defective
Switches
Incorrect setting of change-over switch for
incorrectly
limit signal in FTC625
Permanent alarm
Device configuration changed unintentionally Restore original condition
signal
Device configuration changed
Interrupt or short-circuit line to measuring
transmitter
Measuring transmitter electronics defective
Nivotester defective
Fault indicator
Probe circuit
flashes
(probe, EC27Z/ FEI57S electronic insert or
two-wire cable)
Calibration not
Oscillator in electronic insert does not
possible when
vibrate
probe is covered
Endress+Hauser
Remedy
Check power
Replace Nivotester
Replace FTC625;
connect a fuse into contactor circuit
Replace measuring transmitter
Correctly set change-over switch behind
front panel
Press correction key for 3 s
Check line
Replace measuring transmitter electronics
Replace Nivotester
Check connecting wires
Check connection from electronic insert
to the probe
Check probe for grounding
(Rnom > 200 kOhm)
Replace electronic insert and recalibrate
After the LED goes out, recalibrate and
check function
Calibrate with uncovered probe
Check probe for grounding
en - Trouble-shooting
Note!
A new calibration is necessary:
- if the bridge position of the
EC17Z was changed
- if the electronic insert of the
probe was exchanged.
35