Télécharger Imprimer la page

Lamborghini Caloreclima ECO 3 R Notice D'installation Et D'entretien page 21

Bruleur fioul domestique
Masquer les pouces Voir aussi pour ECO 3 R:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

COMBUSTION CONTROL
In order to obtain the best combustion performance and efficiency, and for respect of the environment,
checksand adjustment of the combustion must be carried out, and with appropriate tools.
Basic values to be considered are:
—CO
indicates the amount of excess air during combustion; if air is increased, CO
2
and if combustion air is decreased, CO
—SMOKE SCALE (Bacharach) indicates that solid un-burnt particles are present in the smoke. If N°2
on the BH scale is exceeded the nozzle must be checked for faults and that it is adapt to the burnerand
boiler (trade, type, pulverization angle).
Usually the BH scale number tends to decrease, increasing pump pressure, in this case keep theincre-
asing combustion levels under control.
—SMOKE TEMPERATURE is a level which indicates heat loss through the chimney; higher thetempe-
rature, greater is the loss and lower combustion efficiency. If the temperature is too high thequantity of
burned light oil needs to be lowered.
IMPORTANT: existing laws in some countries can require a different adjustment to that given here and
may alsohave different parameters. ECO burners are designed to meet the toughest international laws
on energy savingand respect of the environment.
LMO EQUIPMENT
The release pushbutton on the equipment is the main component for accessing all the diagnostic fun-
ctions (activation and deactivation) as well as for releasing the control and checking device.
The release pushbutton has a multicoloured led which indicates the state of the control and checking
device during operation and when the diagnostic function is in use..
Condition
Standby, other intermediate states
Fuel preheating "on", waiting time 5s.max
Ignition stage
Correct operation
Incorrect operation, current level of flame detector
below permitted minimum
Drop in voltage
Burner lock out
Fault
Stray light before burner ignition
Rapid flashing for diagnostics
If the burner is locked out, there will be a steady red light on the lock out pushbutton.
By pressing the transparent pushbutton, the control and checking device will be released.
% values increase.
2
EQUIPMENT STATE INDICATORS
Description
% valuesdecrease,
2
Colour sequence
No light
Yellow
Yellow, flashing
Green
Green, flashing
Alternating yellow red
Red
Red, flashing
Alternating green red
Red, rapid flashing
GB
21

Publicité

loading

Ce manuel est également adapté pour:

Eco 3