Télécharger Imprimer la page

Tripp-Lite SmartOnline SUINT3000RTXL2U Manuel De L'utilisateur page 12

Onduleur en ligne monte en bâti/tour

Publicité

Les langues disponibles

Les langues disponibles

5. Operation
5.4 Front Panel Indicator Lights
Note: All LEDs illuminate during a UPS system self-test.
"ON LINE" LED: This green LED will illuminate continuously to indicate the
UPS system is operating normally in ON-LINE mode (filtering and
resynthesizing AC line input to provide pure sine wave output). When this
LED is illuminated, the load level of the UPS system is displayed on the %
level LEDs (25%, 50%, 75%, 100%).
"LINE" LED: This green LED will illuminate continuously to indicate the
utility-supplied AC line voltage at the wall outlet is nominal. It will flash if
the line voltage is outside the nominal bypass range (either too low or too
high). User action is not required when the LED flashes; the UPS system
remains in normal online mode and will continuously and automatically filter
AC line power to provide equipment with pure sine wave AC power,
regardless of brownout or overvoltage conditions. If this LED is off, then AC
line voltage is not present (blackout) or is at an extremely high voltage, and
the UPS system will provide connected equipment with power from its
battery system.
"BYPASS" LED: This yellow LED will illuminate continuously when the UPS
system is in economy mode. The LED will flash when the UPS system is in
BYPASS mode, indicating that the UPS system's DC/AC inverter is
deactivated. The red "FAULT" LED will also illuminate if the UPS system is in
BYPASS mode due to a fault. During normal operation, the BYPASS LED will
illuminate briefly when the unit is plugged in. If an internal fault or overload
occurs, the LED will flash repeatedly to show that connected equipment will
receive filtered AC line power, but will not receive battery power during a
blackout. In this case, contact Tripp Lite for service.
"FAULT" LED: This red LED will flash when the UPS system detects an
internal fault. If the condition persists after restarting the UPS system, see
Section 6: Troubleshooting.
"LOAD" LED: This green LED will illuminate when the UPS system is
receiving AC power. It also illuminates the % level LEDs (25%, 50%, 75%,
100%) indicating the UPS load level.
"BATT" LED: This green LED will illuminate when the UPS system is
operating from battery power. It illuminates the % level LEDs (25%, 50%,
75%, 100%) indicating the battery charge level. (The "ON BATT" LED will
also be illuminated.)
% Level LEDs: These dual-function LEDs will indicate the % level for either
the load level (if the "LOAD" LED is illuminated) or the battery charge level
(if the "BATT" LED is illuminated).
"OVERLOAD" LED: This red LED will illuminate continuously to indicate the
UPS system's capacity has been exceeded. The UPS alarm will beep
continuously. Immediately unplug some equipment until the LED and alarm
go off. If the overload is not corrected immediately, the UPS system will go
from ON-LINE mode to BYPASS mode.
18-09-247-933652.indb 12
All manuals and user guides at all-guides.com
12
2/13/2019 3:27:30 PM

Publicité

loading

Ce manuel est également adapté pour:

Ag-0264