Troubleshooting
The UPS's control panel lights will turn on in the sequences below to signal that the UPS is
having operational difficulties.
Lights (On/Flashing) and Condition
On: REPLACE BATT
Condition: Replace Battery
On: BATT LOW, ON BATT
Condition: Battery Low
On: BYPASS, LINE, LOAD, OVERLOAD
Condition: On Bypass due to Overload
Flashing: OVERLOAD
Condition: Short Circuit
On: FAULT, 100%
Condition: Battery Voltage too High
On: FAULT, BYPASS, LINE, 50%
Condition: On Bypass due to
High Output Voltage
On: FAULT, BYPASS, LINE
Flashing: 50%
Condition: On Bypass due to
Low Output Voltage
On: FAULT, BYPASS, LINE, 25%
Condition: On Bypass due to High
Bus Voltage
On: FAULT, BYPASS, LINE
Flashing: 25%
Condition: On Bypass due to Low
Bus Voltage
Get user manuals:
See SafeManuals.com
Solution
Let the UPS system charge for at least
12 hours and perform a self test using
the "ON/Test Switch" as described on
page 7. If the light continues to stay on,
contact Tripp Lite for service.
Prepare for imminent UPS shutdown.
Reduce the load the UPS supports.
Remove the cause of the short circuit
from the UPS output.
Restart the UPS. If the problem persists,
contact Tripp Lite for repairs.
Restart the UPS. If the problem persists,
contact Tripp Lite for repairs.
Restart the UPS. If the problem persists,
contact Tripp Lite for repairs.
Restart the UPS. If the problem persists,
contact Tripp Lite for repairs.
Restart the UPS. If the problem persists,
contact Tripp Lite for repairs.