9. Adaptation from 2-wire connection to 3 or
4-wire connection and vice versa
Transmitters with the ordering code 710 – ...D (see Section
4 "Specification and ordering information") are designed for
either a two-wire connection with an output range of
4...20 mA or a three or four-wire connection with an output
range of 0...20 mA.
If, however, a transmitter be changed from one to the other
(see wiring diagrams in Fig. 8), the beginning and end of the
measuring range must be readjusted.
10. Reversing the rotation for
instruments with measuring ranges > 150
A switch is provided on angular transmitters with a measuring
° for reversing the direction of rotation. It is
range > 150
marked S1 (Fig. 10 and Fig. 11).
Take off the cover from the housing.

11. Dimensional drawings

KINAX WT 710
Basic unit
KINAX WT 710
Basic unit with
additional gear
Drilling and cut-out diagram
for fixing with
cheesehead screws
26
Change the position of the switch using a watchmaker's
screwdriver (2.3 mm diam.) and readjust the beginning and
end of the measuring range.
°
6
10.7
3
47
63.1
15
21.5
3
94
110.1
5
M3
Caution! The screw terminals (2.1) Fig. 7
are live.
The 230 V power supply is potentially
dangereous
Attention! In instruments with measuring
°
range less than 150
the switch S1 is
not existing.
Forching a watchmaker's screwdriver
into the opening will damage the PCB.
80
25
80
25
3.2