4. Specification and ordering information

Significance of digits 1. to 5.
Order Code 710 –
1. Version of the transmitter
Standard,
Measuring output non-intrinsically safe
EEx ia IIC T6,
ATEX
Measuring output intrinsically safe
Other versions
2. Sense of rotation
Calibrated for sense of rotation clockwise
Calibrated for sense of rotation counter-
clockwise
For "V" characteristic
Both senses of rotation, calibrated and marked 4
3. Measuring range (measuring input)
°
0 ... 10
°
0 ... 30
°
0 ... 60
°
0 ... 90
°
0 ... 180
°
0 ... 270
Non-standard 0...≥ 5 to 0...< 270
°] to order
"V" characteristic [±

5. Technical data

Measuring input
0...≥ 5 to 0... ≤ 270
Measuring ranges:
(without gear)
Preferred ranges
0...10, 0...30, 0...60, 0...90,
0...180 or 0...270
0...≥ 10
(with additional gear)
Measuring output
Output variable I
:
Load-independent DC current,
A
proportional to the input angle
Standard ranges:
0...1 mA, 3 or 4-wire connection
0...5 mA, 3 or 4-wire connection
0...10 mA, 3 or 4-wire connection
4...20 mA, 2-wire connection
or
0...20 mA, 3 or 4-wire connection
adjustable with potentiometer
4...20 mA, 3 or 4-wire connection
0...20 mA, 4-wire connection
1
2
9
1
2
3
1
2
3
4
5
6
°
9
A
°
°
° to 0...48 turns
4. Output signal (measuring output)
0 ... 1 mA, 3 or 4-wire connection
0 ... 5 mA, 3 or 4-wire connection
0 ... 10 mA, 3 or 4-wire connection
4 ... 20 mA, 2-wire connection
or
0 ... 20 mA, 3 or 4 wire connection
4 ... 20 mA, 3 or 4-wire connection
0 ... 20 mA, 4-wire connection
Non-standard, 3 or 4-wire connection
0 ... > 1.00 to 0 ... < 20 mA
5. Power supply
24 ... 60 V DC/AC,
with electric isolation
85 ... 230 V DC/AC,
with electric isolation
12 ... 33 V DC,
without electric isolation
12 ... 30 V DC (Ex),
without electric isolation
Note
The remaining order code digits concern special features,
e.g. the ancillary gear for extending the measuring ranges.
Non-standard ranges: 0...> 1.00 to 0...< 20 mA
3 or 4-wire connection
External resistance:
R
ext.
(load)
(for instruments with
DC/AC power supply
by AC/DC power pack,
with electric isolation)
R
ext.
(for DC power supply,
without electric isolation)
I
= Output signal end value
A
Accuracy
Reference value:
Measuring range
Limit of error ≤ 0.5% for ranges
Basic accuracy:
0...≤ 150
Limit of error ≤ 1.5% for ranges from
0...> 150 to 0...270
A
B
C
D
E
F
Z
1
2
A
B
12 V
max. [kΩ] =
I
[mA]
A
H [V] – 12 V
max. [kΩ] =
I
[mA]
A
°
°