5. Device programming
5. 1 . Smokescreen and siren function
Start
Positive to give
Negative to
remove
Positive to
remove
Negative to give
5.2. Programming siren sound duration
Device programming
NI-100UN device functions can be configured by setting dip-switches on the
circuit. The following are descriptions of the various configuration parameters.
ATTENTION!
Configuration parameters are read during the RESET
phase or at the time the device is powered.
Both the smoke detector activation input and the siren can be programmed to
achieve maximum compatibility with all existing alarm plants.
In particular, the combination of the Terminating Input switches with the Polarity
switch (unique for both inputs) allow the following startup types:
Switch SW3
Polarity with state of rest
valid for both inputs
SW3
Resting state
ON
0
ON
0
OFF
1
OFF
1
Both inputs have a filter against noise on the row link and the function is activated
only if the startup state remains for at least 1 second.
The sound time of the piezoelectric siren can be programmed via the SW4 switch
of the Siren Time according to the following table:
Follow the input state Siren enable input
ON
(max sound time 15 minutes)
SW-4
OFF
60 seconds
Termination
switch:
SW1 (Smoke)
SW2 (Siren)
OFF
Bringing a positive to the
terminal starts
ON
N.C
removing
starts
OFF
Removing the positive on
the input starts
ON
Bringing a negative to the
input starts
NI-UN
Description
input
to
ground,
the
negative
19