2.1
installation option 1 - open enclosure (enclosure stops short of the ceiling)
NOT Suitable for Dynamic Heat Control™ Plus
It is one option not to finish or close in the top of the enclosure to provide the necessary air circulation path for the
Dynamic Heat Control™ system. Leaving a complete air outlet opening above the enclosure has been found to
be well accepted with respect to final appearance and offer minimal distraction. It also allows for efficient circulation
of air within the room. This option offers the simplest method for framing and installation. (If installing Dynamic Heat
Control™ Plus, refer to option 2 or 3 - DHC Plus cannot be used with option 1). Limit the air outlet opening
height to 4" to reduce the risk of items inadvertly falling into the enclosure. The air outlet opening must extend
around the entire perimeter, or the entire front face of the enclosure, where the enclosure runs from wall
to wall.
DYNAMIC HEAT
CONTROL™ AIR
OUTLET OPEN-
ING IS HOT WHEN
APPLIANCE IS
OPERATING!
Air outlet opening
must be located out of reach of
the user. Air outlet must not be
restricted by furnishings or decor.
2.2
installation option 2 - front opening
Suitable for Dynamic Heat Control™ Plus
Minimum air outlet opening dimensions must be followed. The opening is required to be framed no more than 1.5" below the
enclosure top (see option 2 diagram) to avoid trapping heat in the upper areas and the air outlet opening centered on the appliance
center. Framing the air outlet opening lower will overheat the appliance, the enclosure, and finishing material.
DYNAMIC HEAT
CONTROL™ AIR
OUTLET OPEN-
ING IS HOT WHEN
APPLIANCE IS
OPERATING!
Front air outlet opening must
be located out of reach of the
user. Air outlet must not be
restricted by furnishings or
decor.
Air outlet opening is required to be centered with the appliance.
LVX38
80 sq. in. minimum (Q must be 2-3")
(Q x R)*
S
This dimension is determined from the enclosure height (L) minus the distance to the top of the Dynamic
Heat Control™ air outlet opening (0"-1.5"), height of the air opening (2"-3"), and the distance from the
*Free area. Any trim edging or finishing must not reduce or restrict minimum area. Grills, grates, louvres, or
other unapproved covers are not permitted and will cause a fire hazard.
All manuals and user guides at all-guides.com
(Q x R)*
S
L
MINIMUM AIR OUTLET OPENING DIMENSIONS
LVX50
base of the appliance to the top of the appliance viewing area (25 11/16").
installation planning
2-4"
6" min
Wall mounted
object (picture
frame, appli-
ance, etc.)
2 1/2"
min
0-1.5" Max
2-3"
6" min
Wall mounted
object (picture
frame, appli-
ance, etc.)
LVX62
160 sq. in. minimum (Q must be 2-3")
ceiling
RECOMMENDED
ceiling
enclosure top
must be installed
ALTERNATIVE
LVX74
W415-1739 / C / 08.03.17
EN
5