Installation & Operation Manual
CGS provide a range of detection panels which can be used in many applications such as factories, car parks,
shopping centres and boiler houses. The GDP4 is used with up to twelve (12) gas detectors in a single cable run for
monitoring and detecting gas in zones considered safe including CO, LPG and NG.
The information contained within this manual should be referenced for typical installation and operation only.
For specific requirements that may deviate from the information in this guide – contact your supplier.
Rev: 01
MERLIN GDP4
Safe Area Gas Detector Controller
Installation, Operation & Maintenance
Please read this manual carefully and retain for future use.
Merlin GDP4
1

Publicité

loading

Sommaire des Matières pour CGS Merlin GDP4

  • Page 1 Please read this manual carefully and retain for future use. CGS provide a range of detection panels which can be used in many applications such as factories, car parks, shopping centres and boiler houses. The GDP4 is used with up to twelve (12) gas detectors in a single cable run for monitoring and detecting gas in zones considered safe including CO, LPG and NG.
  • Page 2 Installation & Operation Manual Merlin GDP4 Contents Important Warning Statements ................... 3 Installation ..........................4 Typical Application, Location & Positioning ..................4 Access & Mounting ..........................4 Internal Board Overview ........................5 Board Connections Overview ......................5 Wiring your Detector ......................... 6 BMS Switch ............................
  • Page 3 At the end of their working life, electrochemical sensors for oxygen and carbon monoxide detectors should be disposed of in an environmentally safe manner. Alternatively they can be securely packaged and returned to CGS clearly marked for disposal. Electrochemical sensors should not be incinerated as this may cause the cell to emit toxic fumes.
  • Page 4 Typical Application, Location & Positioning The Merlin GDP4 is a multi-safe zone gas detection panel which can be used in many applications such as factories, car parks, shopping centres and most commonly - boiler houses. It can be used with up to 12 Merlin gas detectors for monitoring and detecting gas including carbon monoxide, liquid petroleum gas and methane.
  • Page 5 Installation & Operation Manual Merlin GDP4 Internal Board Overview 100-120VAC Mains power Input 100-120VAC Gas Solenoid Valve Output. 24VDC Gas detector power supply (Zone 1) 24VDC Gas detector power supply (zone 2) 24VDC Gas detector power supply (zone 3) 24VDC Gas detector power supply (zone 4)
  • Page 6 Installation & Operation Manual Merlin GDP4 Wiring your Detector Power is supplied to a detector via the GDP terminal [+ / -] and using the panel [GAS DETECTION ZONE] terminal. If you are using a GDP panel you will need to use the detector [C/L] terminal as an alarm relay.
  • Page 7 Installation & Operation Manual Merlin GDP4 Factory Set Condition SWITCH CONDITION AUTO RESET ZONE 1 ZONE 2 ZONE 3 ZONE 4 Trouble Shooting Fault. Possible Cause/Correction. Incorrect wiring Detector not responding. Zone switches not properly configured Incorrect Wiring Panel not responding.
  • Page 8 Installation & Operation Manual Merlin GDP4 Mute & Reset Buttons MUTE The mute button is located on the front fascia of the GDP4 and is used to mute the sounder inside the board when in alarm. The internal buzzer operates at approximately >60db measured 30cm (1ft) from a closed panel. The mute button is used to mute the sounder inside the board when in alarm.
  • Page 9 What do I need? Contact your CGS representative for details of suitable bump testing kits and gases. Kits usually consist of a certified gas cylinder; flow control regulator, tube pipe and applicator cone. We recommend only using CGS calibration gas kits to ensure correct flow rates meet CGS technical requirements.
  • Page 10 Installation & Operation Manual Merlin GDP4 End of Operational Life (EOL) The typical life of a gas detector depends on its application and intended target gas, in addition, the operational life can be prolonged if the system and equipment is installed and maintained in accordance the instructions stated within this manual.
  • Page 11 Installation & Operation Manual Merlin GDP4 Page intentionally left blank Rev: 01...
  • Page 12 Every effort is made to ensure the accuracy of this document; however, CGS can assume no responsibility for any errors or omissions in this document or their consequences. CGS would greatly appreciate being informed of any errors or omissions that may be found in the content of this document.
  • Page 13 Veuillez lire attentivement ce manuel et le conserver pour une utilisation future. CGS fournit une gamme de panneaux de contrôle conçus pour être utilisés dans diverses applications telles que les usines, les parkings, les centres commerciaux et les chaufferies. Le GDP4 permet de relier jusqu’à douze (12) détecteurs de gaz sur un seul câble pour surveiller les niveaux de gaz dans les zones sûres considérées comme...
  • Page 14 Manuel d’installation et de fonctionnement Merlin GDP4 Contenu Avertissements importants ..................3 Installation ......................... 4 Application typique, emplacement et positionnement ..............4 Accès et installation ........................4 Vue d’ensemble du panneau interne ..................5 Vue d’ensemble des connexions au panneau ................5 Câblage de votre détecteur ......................
  • Page 15 À la fin de leur vie utile, les capteurs électrochimiques des détecteurs d’oxygène et de monoxyde de carbone doivent être éliminés d’une manière écoresponsable. Ils peuvent également être soigneusement emballés et retournés à CGS clairement marqués comme étant pour élimination. Les capteurs électrochimiques ne doivent pas être brûlés, car l’élément peut dégager une fumée toxique.
  • Page 16 Application typique, emplacement et positionnement Le Merlin GDP4 est un panneau de détection de gaz multizones de sécurité qui peut être utilisé dans de nombreuses applications telles que les usines, les parkings, les centres commerciaux et le plus souvent – les chaufferies.
  • Page 17 Manuel d’installation et de fonctionnement Merlin GDP4 Vue d’ensemble du panneau interne Entrée alimentation secteur 100-120 V AC Sortie électrovanne à gaz 100-120 V AC. Alimentation du détecteur de gaz 24 V DC (zone 1) Alimentation du détecteur de gaz 24 V DC (zone 2) Alimentation du détecteur de gaz 24 V DC...
  • Page 18 Manuel d’installation et de fonctionnement Merlin GDP4 Câblage de votre détecteur L’alimentation est fournie à un détecteur via le terminal GDP [+ / -] et à l’aide du terminal du panneau [ZONE DE DÉTECTION DE GAZ]. Si vous utilisez un panneau GDP, vous devrez utiliser la borne [C/L] du détecteur comme relais d’alarme.
  • Page 19 Manuel d’installation et de fonctionnement Merlin GDP4 COMMUTATEUR DE ÉTAT ZONE 1/2/3/4 Zone de détection de gaz désactivée. Zone de détection de gaz activée. Étalonnage d’usine COMMUTATEUR ÉTAT RÉINITIALISATION AUTOMATIQUE ZONE 1 ZONE 2 ZONE 3 ZONE 4 Dépannage Défaillance.
  • Page 20 Manuel d’installation et de fonctionnement Merlin GDP4 Alarme incendie En cas d’alarme incendie, le voyant LED s’allumera en AMBRE et l’alimentation en sera coupée. L'alarme doit être réinitialisée avant de redémarrer le système. Voyant éteint = OK. Voyant AMBRE = Alarme incendie activée.
  • Page 21 De quoi ai-je besoin? Contactez votre représentant CGS pour obtenir des détails sur les kits de test de déclenchement et les gaz appropriés. Les kits se composent généralement d'une bouteille de gaz certifié, d’un détendeur, d’un tuyau et d’un cône applicateur.
  • Page 22 Vérifier toujours la pression de la bouteille après avoir fermé la vanne - il se peut que la quantité de gaz soit insuffisante! Toutes les bouteilles CGS se referment après le retrait du détendeur/vanne! Attendre toujours au moins cinq (5) minutes entre les tests d'une même unité ou jusqu'à ce que le gaz se soit complètement dispersé!
  • Page 23 Manuel d’installation et de fonctionnement Merlin GDP4 Spécifications techniques Généralités Produit : Contrôleur de détecteur de gaz GDP4 Utilisation : Zones intérieures sûres (à ne pas utiliser dans des atmosphères potentiellement explosives) Indicateurs : Voyants Montage : Montage mural Électrique Consommation d’énergie...
  • Page 24 Tous les efforts sont faits pour assurer la précision de ce document ; toutefois, CGS ne peut être tenu responsable de toute erreur ou omission dans ce document ou des conséquences. CGS aimerait grandement être informé de toute erreur ou omission qui aurait pu être trouvée dans ce document.