J6: Selection of the sensor used for the regulation:
Air: Room sensor only or room sensor with
floor limitation if the external sensor is
connected.
Flr:
limitation
A0: Calibration of the internal sensor
The calibration must be done after 1 day working
with the same setting temperature in accordance
with the following description:
Put a thermometer in the room at 1.5M distance
from the floor (like the thermostat) and check the
real temperature in the room after 1 hour.
When you enter on the calibration parameter "no"
is displayed to indicate no calibration has made.
To enter the value read on the thermometer press
on the (OK) key, the actual value "xx.x" must be
External sensor only, without
11