UL-Data
The safety functions were not evaluated by UL. Listing is accomplished
according to requirements of Standard UL60947, "general use
applications"
Standards:
- ANSI/UL 60947-1, 5
Edition (Low-Voltage Switchgear and Controlgear
th
Part1: General rules)
- ANSI/UL 60947-5-1, 3
Edition (Low-Voltage Switchgear and Controlgear
th
Part5-1: Control circuit Devices an Switching Elements - Electro-
mechanical Control Circuits Devices)
- CAN/CSA-C22.2 No. 60947-1-13, 2
gear and Controlgear - Part1: General rules)
- CAN/CSA-C22.2 No. 60947-1-14, 1
gear and Controlgear - Part5-1: Control circuit Devices an Switching
Elements - Electromechanical Control Circuits Devices)
Nominal voltage U
:
N
DC 24 V:
Altitude:
Switching capacity:
Semiconductor monitoring
outputs:
Switching capacity
Relay output
device free-standing:
Ambient temperature 60°C:
Device mounted without
distances heated by devices
with same load:
Ambient temperature 55°C:
Ambient temperature 60°C:
Voltage range
E1a-E2L, E1b-E3L:
E1a-E2H, E1b-E3H:
Wire connection
Ambient temperature
60°C, 4A bzw. 55°C, 5A:
Ambient temperature
60°C, 8A:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo
nd
Edition (Low-Voltage Switch-
st
Edition (Low-Voltage Switch-
Device must be supplied with a Class 2 or
a voltage / current limited power supply.
≤ 2000 m
24Vdc, 50mA, pilot duty
Pilot duty B300, R300
8A 250Vac G.P.
8A 24 Vdc
Pilot duty B300, R300
5A 250Vac G.P.
5A 24 Vdc
Pilot duty C300, R300
4A 250Vac G.P.
4A 24 Vdc
AC 8 ... 280 V
AC 16 ... 600 V
Min. 75°C aluminum or copper conductors
Min. 90°C aluminum or copper conductors
Troubleshooting
Failure
LED „ON" does not light up
LED „ON" flashes red
LED „ERR" flashes red
LED „ERR" continuously on
Fault handling
When faults are detected on or in the device they are indicated on the
display by an appropriate message. If a reset of the device is necessary
due to the fault, at first the alarm and the associated diagnostic message
have to be acknowledged. Then, the left key has to be pressed for approx.
3 sec. to initiate a reset of the device.
Last status:
E2: 100Hz, E3: 100Hz
Clockwise rotation
Frequency mode 1
R
ü
If a system failure is detected again after restart the device must be replaced
and sent back to manufacturer.
Maintenance and repairs
- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
28
Potential cause
- Power supply A1+/A2
not connected
- Parameterization error
(detailed description on display)
- External failure
(detailed description on display)
- Device failure
(if the failure still exists after restart,
replace device)
M11279_b
UH 6937 / 30.05.22 en / 551A