INSTALLATION INSTRUCTIONS
IMPORTANT: Read before installing fixture. Retain for future reference.
WARNING: Make certain power is OFF before starting installation or attempting any maintenance.
SAFETY: This fixture must be wired in accordance with the National
Electrical Code and applicable local codes and ordinances. Proper
grounding is required to insure personal safety. Carefully observe
grounding procedure under installation section.
WARNING: Make certain power is OFF before starting installation or
attempting any maintenance. Risk of fire/electric shock. If not qualified,
consult an electrician.
TOOLS REQUIRED: Ratchet, 9/16" socket, flat blade screw driver, electrical wiring tools.
INSTALLATION
STEP 1. With housing lying on a smooth, soft surface open the access door by releasing the
latch. Door may be removed by opening approximately 130° and lifting off the hinge.
FIG. 1
STEP 2. Bird guard is provided pre-cut to accommodate 1-1/2" diameter (nominal) mounting
arms. When using larger diameter mounting arms remove the punch out section of
the bird guard.
STEP 3. Using a 9/16" socket, loosen the two or optional four pipe clamp mounting bolts
enough to allow mounting arm (not included) to slide onto leveling steps. FIG. 2
STEP 4. Close access door. Lift the housing into place, re-open access door, and position
end of mounting arm onto leveling steps so that housing is level. Care must be taken
so arm does not in advertently strike internal components. To avoid potential
damage to fixture, ensure housing is level both front to back and side to side by
placing level on flat surface on top of the housing.
STEP 5. Using a 9/16" socket tighten the two or optional four pipe clamp mounting bolts to
16-18 ft-lbs.
WIRING
STEP 1. Pull service wires through mounting arm and into housing approximately 10".
STEP 2.
a. Three-terminal block (2-wire service): Connect line service lead to terminal that is
connected to black factory-installed wire. Connect neutral service wire to terminal
that is connected to white factory-installed wire.
b. Three-terminal block (3-wire service, 2 lines, 1 ground): Connect 1 line service
lead to terminal that is connected to black factory-installed wire. Connect other
line service lead to terminal that is connected to white factory-installed wire.
Connect ground service lead to terminal that is connected to green
factory-installed wire.
c. Three-terminal block (3-wire service, 1 line, 1 neutral, 1 ground): Connect line
service lead to terminal that is connected to black factory-installed wire.
Connect neutral service wire to terminal that is connected to white
factory-installed wire. Connect ground service wire to terminal that is connected
to
green factory-installed wire.
d. No terminal block (3-wire service, 2 lines, 1 ground): Connect 1 line service
lead to black factory-installed wire. Connect other line service lead to white
factory-installed wire. Connect ground service lead to green factory-installed
wire.
e. No terminal block (3-wire service, 1 line, 1 neutral, 1 ground): Connect line
service lead to black factory-installed wire. Connect neutral service wire to white
actory-installed wire. Connect ground service wire green factory-installed wire.
NOTE: SEE WIRING DIAGRAM FOR ADDITIONAL WIRING DETAILS.
STEP 3. Position and secure all wires away from all other electrical components (drivers,
terminal blocks).
STEP 4. Close access door and secure latch.
These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide directions for meeting every possible
contingency during installation, operation or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for user's purpose, please
contact your nearest representative. NOTE: Specifications and dimensions subject to change without notice.
Cooper Lighting Solutions
1121 Highway 74 South. Peachtree City, GA 30269
• RISK OF ELECTRIC SHOCK—Disconnect power at fuse or circuit
breaker before installing or servicing.
• RISK OF BURN—Disconnect power and allow fixture to cool before
servicing.
• RISK OF PERSONAL INJURY— Fixture may become damaged and/or
unstable if not installed properly. Tighten all fixture components to their
recommended torque values. Do not lift pole into place by securing
lifting device to lighting fixture or mounting arm.
Latch
Optional Photocontrol Receptacle
FIG. 1
(2) Fully Threaded Bolts
Terminal Block
© 2020 Cooper Lighting Solutions. All Rights Reserved. Publication No. ADW131406 September 2013
www.cooperlighting.com
XNV2
LED Roadway, Area and
Site Luminaire
Sheet 1 of 2
IMI-806
120°
Door
Hinge
Housing
Bird Guard
Pipe Clamp
Leveling Steps
FIG. 2