Relay remote commands
If the switches 'S1', 'S2' are available on the power print and set to "OUT", then two relay outputs can be operated via the heat meter. If
the function programming of the relay ("OUTPUTS" / "FCT") is set to "M-Bus", then these can be switched on or off via the remote com-
mands (MBus or LON):
NviSetRelais1
NviSetRelais2
Network variables
®
With LONWORKS
networks, nodes communicate their measured values and parameters using Standard Network Variables (SNVs) to oth-
er network nodes of the same network. If they are changed by node-specific firmware, the operating system of Neuron automatically adopts
the communication of the new value via the network. Which of the communication connections of the system are carried out is determined
in "binding" (no further details are available here).
®
CALEC
ST only uses variables with Standard Network Variable types (SNVT Master list Version: 10.00), to ensure binding without prob-
lems.
The network variables are subdivided into logical groups. These groups are designated objects. In CALEC
Information", which provides more detailed information about all the nodes using the heat meter-specific profile 'Utility Data Logger Reg-
ister #2110' "Current Values" for the current meter status; "Memory 1" for the memory 1 values and "Freeze Memory" for the frozen me-
ter readings. In addition 'Open-Loop Sensor Object #1' "Instant Values" provides information on the actual values (temperatures, power,
flowrate and density), and the 'Open-Loop Actuator Object #3' "Relay 1" and "Relay 2" for control of the relays.
Memory values
®
®
The CALEC
ST as LONWORKS
Along with the current data, a total of two memory data sets are available. These are:
• The preset day values for Memory 1 in profile: 'Utility Data Logger Register #2110': "Memory 1"
• The freeze data (frozen values) in profile: 'Utility Data Logger Register #2110': "Freeze Data".
No. /
NV-Variable
Data
Obj.
Unit
Node Object #0: "Node Information"
1 / 0
nviRequest
Structur / -
2 / 0
nvoStatus
Structur / -
3 / 0
nviSetTime
Structur / -
8 / 0
nvoFileDirectory
Structur / -
12 / 0
nvoOpTime
float / [Sec.]
13 / 0
nvoErrTime
float / [Sec.]
14 / 0
nvoSerialNo
ASCII / -
15 / 0
nvoManufDate
Structur / -
16 / 0
nvoTime
Structur / -
17 / 0
nvoDevice
ASCII / -
18 / 0
nvoComment
ASCII / -
ncoDevice
ASCII / -
ncoSerialNo
ASCII / -
ncoHWVersions
ASCII / -
ncoFWVers_Calc
ASCII / -
ncoFWVers_Appl
ASCII / -
ncoFWVers_Host
ASCII / -
Bit 0 of SNVT variables controls the status of relay 1 (OL Actuator Object): "Relay 1"
Bit 0 of SNVT variables controls the status of relay 2 (OL Actuator Object): "Relay 2"
does not make available as network variables all those memory data sets stored in the counter.
SNVT
Obj.
SNVT_obj_request
SNVT_obj_status
SNVT_time_stamp
SNVT_address
SNVT_time_f
SNVT_time_f
SNVT_str_asc
SNVT_time_stamp
SNVT_time_stamp
SNVT_str_asc
SNVT_str_asc
UCPT_str_asc
UCPT_str_asc
UCPT_HWVersions
UCPT_FWVers_Calc "FW 1.01.00"
UCPT_FWVers_Appl "FW 1.00.00"
UCPT_FWVers_Host "FW 1.00.00"
Range of values
Designation
Status promt
Status message
0..3000 J. / 0..59 Min.
Set date / time
0..1E38 Sec.
Operating time counter
0..1E38 Sec.
Time-off counter
"00000000..99999999"
Serial number
0..3000 J. / 0..59 Min.
Manufacturing date
0..3000 J. / 0..59 Min.
Date / time
"Calec ST"
Device tag
"Aquametro AG..."
Customer text field
"Calec ST"
Device tag
"00000000..99999999"
Serial number
"HW 99.99.99.99"
Hardware Version
Firmware Version Calc.
Firmware Version Neuron
Firmware Version Host
®
ST are 'Node Object #0' "Node
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
17