Environmental conditions

100
90
80
70
60
50
40
30
20
10
0
-30°
-50°
Battery: Alkaline 9V type 6 LR 61
Consumption: 8.6 mA typical, 12 mA max
Service life: 55 h typical, 40 h min.
Indicator: Green light goes out for a battery voltage < 6.5 V
Class of protection: Class II
Dielectric strength: 4 kV
Leakage current: < 0.5 mA
I To make a current measurement, switch on the clamp by selecting the 100 mV/A range.
Check that the battery indicator (green) is lit and that the «OL» indicator is not lit.
I Connect the clamp to the oscilloscope.
With the clamp closed and without clamping a conductor, select the highest sensitivity
(for example 1 mV/cm) on the oscilloscope and 100 mV/A on the clamp, then set zero on
the clamp with the thumbwheel in relation to a reference chosen on the oscilloscope. Zero
on the oscilloscope makes it possible to adjust this setting.
I Select the measurement sensitivities of the clamp and the oscilloscope.
I Choose the connection method which is the best adapted to measurement on the
oscilloscope.
I Note the direction of the primary current by means of the arrow marked on and under the case.
I Insert the conductor carrying the current to be measured in the clamp and take the
measurement.
I If necessary, re-check the origin of the graph, with the jaws not clamped around the
conductor, and make the measurement again.

GENERAL SPECIFICATIONS

3
2
1
2
-10°
10°
30°

OPERATING MODE

16
1 Reference range
2 Working range
3 Storage range
3
50°
70°
90°
Temperature in °C