BRÖTJE RGB Montage / Réglage page 34

Appareil ambiant
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 13
Installation
GB
34
Connections
The remote control RGB has to be connected to the terminal FB of
the controller RVS or LMU74.
Terminal
Designation
1
CL +
2
CL -
Cable lengths
Bus cables have not mains voltage but protective low voltage.
They must not be routed in parallel to the mains cables (interfe-
rence signals). Otherwise shielded cables should be used.
Permitted cable lengths:
Cu-cable up to 20 m: 0.8 mm
Cu-cable up to 80 m: 1 mm
Cu-cable up to 120 m: 1.5 mm
Cable types: e.g. LIYY or LiYCY 2 x 0.8
Caution! When using an RGB and RGT on an LMU7, the RGT-connec-
tion must be carried out as a 3-wire connection (terminal 1, 2 and
3).Otherwise, the right to claim under garantee becomes invalid.
Application
RGB Data
RGB Mass
2
2
2