LA NORDICA CUCINOTTA Instructions Pour L'installation, L'utilisation Et L'entretien page 20

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Should it be necessary to exceed the ridge of the roof, the chimney cap must assure the discharge also in
case of windy weather (Picture 4).
The chimney cap must meet the following requirements:
have internal section equivalent to that of the stack.
have a useful output section twice as big as the flue internal one.
be manufactured in such a way as to prevent the penetration of rain, snow, and any other foreign
body in the flue.
be easily checkable, for any possible maintenance and cleaning operation.
(1)
Industrial chimney
cap with pre-fabricated
elements – it allows an
excellent discharge of the
smokes.
50 cm
2 m
1
m
20
10 m
(1)
from walls, pitches and trees. Otherwise raise it of at least 1 m
over the hindrance.
The chimney cap must exceed the ridge of the roof of at least
1 m.
>A
H min.
(1)ridge axis
α
(2)
Handicraft chimney
cap. The right output
section must be at least
twice as big as the
internal section of the flue
(ideal value: 2.5 times).
(1) In case of flues side by side, a chimney cap
must be higher than the other one of at least 50 cm
in order to avoid pressure transfers between the
flues themselves.
The chimney cap must not show hindrances within 10 m
> _ A
0,5 m
(2)roof
CUCINOTTA – CUCINOTTA Forno
(3)
Chimney cap for steel
flue with internal cone
deflector of smokes.
7093101 – Rev.06 – EN
Picture 4
Picture 5
Picture 6
Picture 7