Positioning of combs
After cleaning the recovery unit make sure the combs are positioned correctly, as shown
in fig. 36. Tighten the nuts on the compressor disk "A" respecting the torque setting of
0.6 Nm. If a torque wrench is unavailable, check that there is a fume passage of 1 mm
between the coils.
60°
60°
60°
fig. 36 - Positioning of combs
4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault,
the display will flash together with the fault symbol (detail 22 - fig. 1) indicating the fault
code.
There are faults that cause permanent shutdowns (marked with the letter "A"): to restore
operation, press the RESET button (detail 8 - fig. 1) for 1 second or use the RESET on
the remote timer control (optional) if installed; if the boiler does not restart it is necessary
to eliminate the fault indicated in the operation LEDs.
Other faults cause temporary shutdowns (marked with the letter "F") which are automat-
ically reset as soon as the value returns within the boiler's normal working range.
Some faults linked to the circulating pump are signalled by the LED located around the
speed selector (fig. 37).
60°
60°
60°
fig. 37
cod. 3541G830 - Rev. 01 - 10/2016
ATLAS D 32 CONDENS SI UNIT
Table. 4 - List of faults
Fault
Fault
code
A01
Burner block
Flame present signal
A02
with burner off
Overtemperature pro-
A03
tection activation
A04
Card parameter fault
Preheater fault (the
F07
contact does not close
in 120 seconds)
F09
Card parameter fault
F10
Delivery sensor 1 fault
F11
Card parameter fault
F12
Card parameter fault
F14
Delivery sensor 2 fault
F16
Card parameter fault
Supply voltage under
F34
170V.
Faulty mains fre-
F35
quency
Incorrect system water
F37
pressure
F39
External probe fault
Incorrect system water
F40
pressure
A41
Sensor positioning
F42
Heating sensor fault
System water pressure
F47
sensor fault
Possible cause
Cure
Pump blocked
Replace
Faulty electric motor
Replace
Faulty oil valve
Replace
No fuel in tank, or water on bottom
Refill with fuel or suck the water
Oil line feed valves closed
Open
Dirty filters (line-pump-nozzle)
Clean
Pump unprimed
Prime and find the cause of
unpriming
Ignition electrodes not properly adjusted,
Adjust or clean them
or dirty
Nozzle clogged, dirty or deformed
Replace
Unsuitable head and shutter adjustments Adjust
Faulty electrodes or earthed
Replace
Faulty ignition transformer
Replace
Faulty electrode wires or earthed
Replace
Electrode wires deformed by high tem-
Replace and protect
perature
Faulty valve or transformer electrical con-
Check
nections
Broken pump-motor joint
Replace
Pump inlet connected to return pipe
Correct the connection
Faulty photoresistance
Replace
Dirty photoresistance
Clean the photoresistance
Photoresistance short circuit
Replace the photoresistance
Extraneous light strikes the photoresist-
Eliminate the light source
ance
Check the correct positioning and
Heating sensor damaged
operation of the heating sensor
Check the circulating pump.
No water circulation in the system
(See table 5)
Air in the system
Vent the system
Check the card parameter and
Wrong card parameter setting
modify it if necessary
Preheater fault
Check the preheater
Wiring disconnected
Check the wiring
Check the card parameter and
Wrong card parameter setting
modify it if necessary
Sensor damaged
Check the wiring or replace the
Wiring shorted
sensor
Wiring disconnected
Check the card parameter and
Wrong card parameter setting
modify it if necessary
Check the card parameter and
Wrong card parameter setting
modify it if necessary
Sensor damaged
Check the wiring or replace the
Wiring shorted
sensor
Wiring disconnected
Check the card parameter and
Wrong card parameter setting
modify it if necessary
Electric mains trouble
Check the electrical system
Electric mains trouble
Check the electrical system
Pressure too low
Fill the system
Sensor damaged
Check the sensor
Check the wiring or replace the
Probe damaged or wiring shorted
sensor
Probe disconnected after activating the
Reconnect the external sensor or
sliding temperature
disable the sliding temperature
Check the system
Pressure too high
Check the safety valve
Check the expansion tank
Check the correct positioning and
Delivery sensor not inserted in boiler shell
operation of the heating sensor
Sensor damaged
Replace the sensor
Wiring disconnected
Check the wiring