CHIMNEY CAPS - DISTANCES AND POSITIONING
Inclination of the
roof
¡
15°
30°
45°
60°
6.
VENTILATION HOOD OR ADJACENT LOCAL
In order to distribute the heating in the environment or carry it to an adjacent room it is possible to install a galvanized
steel covering (optional) on the external cast-iron body of the same appliance.
The covering is provided with 4 outlets with a 150mm diameter to connect the heat resistant pipes. This covering is
fixed to the fireplace through special screws.
a) Perform the drilling on the walls or on the existing hood to allow the passage and the application of the (fire-
resistant) hoses with 15cm diameter and related openings.
b) Fasten the hoses using the clamps to the related collars and openings.
22
10 m
(1) The chimney cap must not show hindrances within 10 m from
walls, pitches and trees. Otherwise raise it of at least 1 m over the
hindrance.
The chimney cap must exceed the ridge of the roof of at least 1 m
>A
H min.
(1)Asse colmo
Distance between the roof
ridge and the stack
A (m)
< 1,85 m
> 1,85 m
< 1,50 m
> 1,50 m
< 1,30 m
> 1,30 m
< 1,20 m
> 1,20 m
> _ A
0,5 m
(2)Tetto
Minimum height of the stack
(measured from the outlet)
0.50 m above the roof ridge
1.00 m from the roof
0.50 m above the roof ridge
1.30 m from the roof
0.50 m above the roof ridge
2.00 m from the roof
0.50 m above the roof ridge
2.60 m from the roof
FOCOLARI in ghisa
Picture 10
(1) Ridge axis
(2) Roof
Picture 11
UNI 10683/98
H (m)