Signal inputs
Max. CAN cable length in networks
Input voltage
Max. current consumption
Permissible operating temperature
Permissible storage temperature
Dimensions (H x W x D)
Weight
2014.08 | 4.0 | F.01U.258.925
IN1/IN2
Lmax = 1000 m, depending on configuration, cable type and topology
20 V DC to 30 V DC
–
Standby: 135 mA at 24 V DC
–
During alarm: 225 mA at 24 V DC
-5 °C to +50 °C
-20 °C to +70 °C
190 mm x 404 mm x 60 mm
Approx. 2 kg
Installation Guide
Panel Controller
Bosch Sicherheitssysteme GmbH