Technical description
3.2 Dimensions
155
Illustr. 3: Dimensions in mm
3.3 Functional description
The "Unibox T RTL" is intended for individual
room temperature control and for limiting the
return temperature for a surface temperature
balance.
The integrated thermostatic valve is equipped
with a presettable valve insert and thus enables
the flow rate to be accurately adapted to the
required heat demand (see chart in the appen-
dix) and hydraulic balancing to be carried out.
The installation position of the "Unibox T
RTL" should be chosen so that fluid flows first
through the heating circuit and then through the
"Unibox T RTL" valve. The heating fluid cools
down between the entry point to the heating
surface and reaching the "Unibox T RTL". The
flow rate is controlled by the sensor element
located in the volume flow. The self-acting
thermostat controls the desired room tempera-
ture. The temperature of the surface tempera-
ture balance can be corrected by turning the
handwheel of the return temperature limiter
(see 3.4.1 on page 28). The desired room
temperature can be set by turning the hand-
wheel of the automatic thermostat.
3.4 Operating elements
3.4.1 Return temperature limiter
You can set the desired fluid temperature for
the surface temperature balance with the hand-
wheel. The return temperature limiter integrated
in the valve detects the fluid temperature being
28
57
210
transported and opens and closes the valve
accordingly.
The recommended control range is
between approximately 25 °C and
approximately 40 °C.
3
2
1
Illustr. 4: Handwheel
(1)
Valve with presettable insert and inte-
grated return temperature limiter
(2)
Graduation figure
(3)
Handwheel
Graduation figure
0
10
20
25
30
35
40
-
Unibox T RTL
Temperature
(Valve fully closed)
10 °C
20 °C
25 °C
30 °C
35 °C
40 °C
(Valve fully open
until a temperature of
approximately 43 °C
has been reached)
102273380-V01.06.2019