8. APPENDIX
9. App end ix
8.1 Réglage des paramètres du FC 101
Parameter
Description
1-00
Configuration
1-03
Torque characteristic
1-20
Motor power
1-22
Motor voltage
1-23
Motor frequency
1-24
Motor current
1-25
Motor speed
1-90
Motor protection
Motor protection
1-93
Connection
Connection
3-02
Minimum Reference
3-03
Maximum Reference
3-41
Ramp up time
3-42
Ramp down time
4-12
Motor Speed low
4-14
Motor Speed high
4-19
Max Output Frequency
5-40
Relay output 1-3
6-10
Low voltage
6-11
High voltage
6-15
Terminal 53 High Ref.
6-19
Terminal 53 mode
Value
0
1
*
400
50
*
*
2
4
6
0
0
*
150
100
15
*
*
9
0
10
*
1
** Thermistor connection at terminal 29 and 50
All other parameters are standard Danfoss factory settings.
Function / unit
Process open loop
Variable torque medium
kW
V
Hz
A
rpm
Thermistor trip
ETR Trip
Digital input 29
No thermistor
Hz
Hz
Sec
Sec
Hz
Hz
Hz
Alarm
V
V
Hz
V
26
Comment
* See motor plate
* See motor plate
* See motor plate
With thermistor
No thermistor
With thermistor
No thermistor
* Max motor frequency
* Max motor frequency
* Max motor frequency
* Max motor frequency