TROUBLESHOOTING (cont.)
The LED and the LCD
displays are off.
The reaction of
the door does not
correspond with the
LED signal.
The LCD or remote
control does not react.
Visible External
Monitoring / Test
Indication LED (red)
does not flash.
Visible External
Monitoring / Test
Indication LED (red)
flashes continuously
Door cycles open and
remains open
Page 8 of 9
No power to sensor.
Incorrect output
configuration / wiring.
The sensor is protected by
a password.
Monitoring installation/set-
up error.
Sensor and/or wiring
malfunction.
Wiring issue
Control not set correctly
Door control monitoring
set to Active High.
Check wiring.
Check for correct power supply.
Check output configuration setting.
Check wiring.
Enter the correct password. If you forgot the
code, cut and restore the power supply to access
the sensor without entering a password during
1 minute.
Verify door control is capable of monitoring
and the sensor monitoring wires are properly
connected to the door control.
Verify monitoring (TEST) is on in the sensor
settings.
Verify that there are no breaks anywhere in the
wire harness.
Replace the sensor.
Verify wiring.
Verify control monitoring set to Active Low.
Set door control monitoring to Active Low.
75.5784.11 IXIO-DT1 UL INDUSTRIAL 20180305