3A
PROGRAM / WEEK
This menu item is provided for the simple input of programs which are to be repeated weekly (such as switching of lights and boilers).
A weekly program consists of an ON time, an OFF time and the associated ON and OFF days.
• MON TO SUN: the days of the week are already assigned and you only need to set the ON and OFF times. This is used where the same pro-
gram is to be
executed on every day of the week.
• INDIVIDUAL: you can assign the ON and OFF times to any desired days. This is used where the same program is to be executed only on
certain days of the week or different programs are to be executed on the various days.
OR function
The programs defined for each channel are ORed together. In other words, the output will be active if this is defined in any of the programs.
Example: channel 1
Prog. 1
Prog. 2
Channel-1 relay
Sample WEEK program
The timer is to switch on at sunset on each day of the week and switch off at sunrise.
3B
PROGRAM / YEAR
This menu item permits the input of (additional) annual programs which are to be executed only during a specified period. These programs and
the weekly programs of the same channel are ORed together as described above.
The period during which a program is to be executed is defined by entering a start date and an end date.
• The option EVERY YEAR should be selected if the additional program is to be executed during the same period of each year
(e.g. Christmas, national holidays, birthdays, etc.).
• The option ONCE should be selected if the additional program is to be executed only during a single period (e.g. vacation period), but the
start and end dates of this period are different in each year.
Sample YEAR program
Channel 2 is to be activated each year on at 09:00 hours on 01.11. and deactivated at 23:00 hours.
3C
The weekly and annual programs defined for a channel are not executed as long as an extra program is active.
However, other exception programs will be executed while an exception program is active.
The various exception programs are ORed together as described above. (see OR function 3a)
• The option EVERY YEAR should be selected if the exception program is to be activated for the same period in each year
(e.g. Christmas, national holidays, birthdays, etc.).
• The option ONCE should be selected if the exception program is to be activated only during a single period (e.g. vacation period), but the start
and end dates of this period are different in each year.
• Option MON TO SUN: the exception program is active from 00:00 hours on the start date to 24:00 hours on the end date.
During this period, the output of the related channel switches only as defined in the exception program.
• Option INDIVIDUAL: the exception program is active from 00:00 hours on the start date to 24:00 hours on the end date.
During this period, the output of the related channel switches only as defined in the exception program.
• Option PROG ON: the exception program is active from the ON time on the start date to OFF time on the end date. During this period, the output
of the channel is permanently on.
• Option PROG OFF: the exception program is active from the ON time on the start date to OFF time on the end date. During this period, the
output of the channel is permanently off.
Sample EXCEPTION programs
ON at sunset
OFF at sunrise
ON / OFF at programmed time
3D
PROGRAM / EXCEPTION
Channel 2 is to be switched off each year for the entire period 01.08. to 31.08.
Each year from 25.12. to 26.12., channel 2 is to be switched on at 6:00 hours, switched off at sunrise, switched on at sunset and switched
off at 23:00 hours. For this, two programs are needed:
Program 1: ON at 6:00 and OFF at sunrise
Program 2: ON at sunset and OFF at 23:00
PROGRAM