420010310600 BLU 7000.1 - 12000.1 PR TS
EN
IONIZATION CURRENT
The ionization current is checked by inserting a
microammeter with an end of scale of 50 µA (d.c.)
min. 6 μA
in series with the ionization probe.
24
A faulty position of the electrode can lead to a
reduction in the ionization current and cause a
LANDIS LFL1.622
safety cut-out of the burner due to a flame detec-
Microamperometro �
Microammeter
tion failure. In this case, check the position of the
fondo scala 50 μA
50 μA end of scale
electrode, its electric connection and the earthing
of the burner. The ionization current is normally > 20 µA.