Eaton CROUSE-HINDS Serie Information Sur L'installation Et L'entretien page 3

Masquer les pouces Voir aussi pour CROUSE-HINDS Serie:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

WIRING DIAGRAMS
LOOSEN BOLTS TO SET
LUMINAIRE ANGLE
5/16-18 ANGLE BOLT
LOOSEN BOLTS TO SET
LOOSEN BOLTS TO SET
FLOODLIGHT ANGLE
LUMINAIRE ANGLE
PIVOT
1/2-13 BOLT
3.
Re-install back cover/heat sink and tighten all nine (9) mounting screws to 22 in.-
lbs. (2.5 N-m). Be sure wires are not pinched during cover installation.
Replace any damaged or missing cover screws. Use only stainless steel
#10-24 x 0.75"cover screws.
4.
To make final vertical adjustment, loosen the pivot bolts on the luminaire yoke to
position luminaire at the desired angle.
5.
Rotate the luminaire housing to the desired position.
6.
Tighten the two (2) pivot bolts to 45 ft.-lbs. (61 N-m).
7.
Turn power on.
To avoid ignition of the hazardous atmospheres or overheating of the
luminaire:
Do not position the luminaire beyond the aiming range limits.
IF 1883 • 02/20
13L - 15L WIRING UNV34
HEATSINK
GREEN/YELLOW
DRIVER HOUSING
LINE
NEUTRAL
POSITIVE
NEGATIVE
GROUND
AIMING RANGE
105°
45°
45° PAST
VERTICAL
Figure 4
WARNING
Copyright
SUPPLY WIRE
G
N
L
BLACK
WHITE
(DC-)
(DC+)
G
N
L
G
N
L
(GREEN)
(WHITE)
(BLACK)
INPUT
DRIVER
OUTPUT
+ (RED)
- (BLACK)
(YELLOW/BLACK)
(YELLOW/RED)
S1 -
LED PCB 1
S2 -
S2 +
(JUMPER WIRE - BLACK)
S1 +
Figure 3
Input wire location
Input wire location
Ground lug location
60°
(torque to 25 in.-lbs.
60° BEFORE
EXTERNAL GROUND INSTALLATION INSTRUCTIONS
VERTICAL
1.
Unscrew the ground lug fastener shown in Figure 5.
2.
Install stripped ground wire (0.5" [12.7mm]) in ground lug.
Note: Wire range from AWG 14 - 12 [3.31 - 2.08 mm2]
3.
Torque ground lug fastener down on ground wire. Torque to 25 in.-lbs. [2.82
N-m], as shown in Figure 5.
2020, Eaton's Crouse-Hinds Division
®
3X
3 POLE SPLICE
CONNECTOR
Leads not used
3X
2 POLE SPLICE
CONNECTOR
BLACK/WHITE
PURPLE (+)
GRAY (-)
BLUE/WHITE (OTP+)
PINK (OTP+)
2X
2 POLE SPLICE
CONNECTOR
B
Ground Lug Location
[2.82 N-m])
(Torque to 25 in.-lbs.)
Figure 5
DIMMING LEADS
0-10 VDC SIGNAL
10V = 100% LIGHT OUTPUT
DIMMER
0 - 10VDC
Mounting
screw
Mounting Screw
(torque to
(Torque to 19 in.-lbs.)
19 in.-lbs.
[2.15 N-m])
Page 3

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Crouse-hinds unv1Crouse-hinds unv34

Table des Matières