Appliance Configuration - Iom CWAR 01-N-3ALL Manuel D'installation Et De Maintenance

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

13.3. APPLIANCE CONFIGURATION

13.3.1. FACTORY CONFIGURATION
Type
J1
J2
RC
OFF
OFF
SH
OFF
ON
ST
ON
OFF
RH
ON
ON
Jumper
OFF
J6
ON
13.3.2. CLIENT SETTINGS
Jumper
OFF
J3
ON
OFF
J4
ON
OFF
J5
ON
Cooling and thermodynamic Heating
Thermodynamic Cooling + thermodynamic
Heating or electric heating depending on
appliance return water temperature
Cooling only
Cool + heat by electric heat
Configuration
Normal mode
Forced mode dry contact (remote ON/OFF)
Configuration
the fan is controlled via the compressor and the ICT
sensor in Heating mode.
the fan operates continuously in Heating mode,
except in OFF mode.
No anti-stratification mode
Anti-stratification mode active. Fan cycling
ambient temperature is measured at the RCL.
ambient temperature is measured with the Return
sensor (RT) located on the appliance.
18
Description

Publicité

Table des Matières
loading

Table des Matières