13. RCL AND µBMS CONTROL MODULES WIRING

13.1. RCL

Unscrew the lower screw on the RCL control.
Separate the RCL control from its support bracket with the help
of a flat bladed screwdriver
Checking the support bracket :
Ensure that the wall surface is completely flat at the point where you wish to install the RCL control, as it is important
that the support bracket is not twisted on installation, because any bending could lead to the control not clipping
together properly and result in operating difficulties.
Fitting the support bracket :
²
Present the support bracket to the desired location and align it with a spirit level.
²
Mark the screw locations.
²
Make a hole or install appropriate plugs according to the material (wood, concrete, plasterboard etc.).
²
Screw the support bracket to the wall, preferably with round head screws matching the following
The RCL control module must be connected in accordance with the diagram
below.
Use twisted pair telephone wire with a section of between 0.12 and 0.5 mm²
for wiring the control modules.
Take care to comply with the terminal connection reference numbers.
LED
characteristics :
- Minimum length : 15 mm,
- Maximum head diameter : 7 mm,
- Maximum thread diameter : 3.5 mm,
- Head protrusion : 3.5 mm.
Support
bracket
15
Lower screw
1 2 3 4