11.5) DEFAULT MENU (default)
Restores the controller's default factory settings. Following this reset, you will
need to run the AUTOSET function again.
11.6) AUTOSET MENU (AUTOset) FIG. G
Enables Motor Torque to be set automatically along with relevant slow-down.
Before running the AUTOSET function, adjust slow-down speed (Fig. F).
WARNING! The AUTOSET operation must be performed starting from the
closing limit switch position. If you attempt to run the AUTOSET function
in any other position, the following error message will appear: " o" and the
operation will not be performed.
12.1) TABLE A: PARAMETERS MENU (PARA )
Parameter
min.
max.
0 sec.
120 sec.
TCA
1%
99%
slow. speed
30
250
t. start
1%
99%
op. t . s low
1%
99%
cls. t
0
127
Zone
op. d ist slow
(special par. 6)
0
99%
cl. d ist slow
(special par. 7)
12.2) TABLE B: LOGIC MENU (logic)
Logic
Default Definition
Automatic
OFF
TCA
Closing Time
Block Pulses
OFF
ibl open
opening
OFF
Block Pulses TCA
ibl tca
3 step/4 step
OFF
3 step
Pre-alarm
OFF
pre-alar
Photocells
OFF
photoc. o pen
during opening
Fast closing
OFF
fast cls.
OFF
Photocell test
test phot
Master/slave
OFF
aster
INSTALLATION MANUAL
default
personal Definition
Automatic Closing Time
120 sec.
Slow-down speed
50%
150
Inrush time
25%
Opening motor torque
Closing motor torque
25%
Zone
0
Opening slow-down
distance
20%
Closing slow-down
distance
Cross out
setting
Description
used
ON
Switches automatic closing on.
OFF
Switches automatic closing off.
ON
The start pulse has no effect during opening.
OFF
The start pulse has effect during opening or closing.
ON
The start pulse has no effect during TCA pause.
OFF
The start pulse has effect during TCA pause.
Switches to 3-step logic. A start pulse has the following effects:
door closed: opens
ON
during opening: stops and switches on TCA (if configured).
door open: closes
during closing: stops and opens again
Switches to 4-step logic. A start pulse has the following effects:
door closed: opens
during opening: stops and switches on TCA (if configured)
OFF
door open: closes
during closing: stops and does not switch on tca (stop)
after stop: opens
ON
The flashing light comes on approx. 3 seconds before the motors start.
OFF
The flashing light comes on at the same time as the motors start.
When beam is broken, operation of the photocell is switched off during opening. During closing,
ON
movement is reversed immediately.
When beam is broken, photocells are active during both opening and closing. When beam is broken
OFF
during closing, movement is reversed only once the photocell is cleared.
ON
Closes 3s after the photocells are cleared before waiting for the set TCA to elapse.
OFF
Command not enabled.
ON
Switches photocell testing on
Switches photocell testing off
OFF
If disabled (OFF), it inhibits the photocell testing function, enabling connection of devices not
equipped with supplementary test contacts.
Control panel is set up as the Master unit in a centralized serial connection system.
ON
WARNING: the control panel set as the master must be the first in the series.
OFF
Control panel is set up as a Slave unit in a centralized serial connection system.
https://appceso.com
WARNING!! The AUTOSET operation must be performed only once you have
checked that the leaf is moving accurately (opening/closing) and that the
limit switches are tripping correctly.
During this stage, it is important to avoid breaking the photocells' beams and
not to use the START, STOP and commands or the display.
WARNING! While the AUTOSET function is running, the obstacle detection
function is not active. Consequently, the installer must monitor the auto-
mated system's movements and keep people and property out of range of the
automated system.
When using buffer batteries, the AUTOSET function must be run with the control
panel running off mains power.
Description
Pause time before automatic closing.
Set slow-down speed, choosing a percentage value of the ma-
ximum speed.
Inrush time at each motor startup, during which time obstacle
detection is not active.
Given in hundredths of a second (150=1.5 s).
Sets motor's operating force during opening at normal speed.
Sets motor's operating force during closing at normal speed.
Serial connection address.
Set the Zone number in the range 0 to 127. The zone number
allows you to create groups of automated devices, each of which
answers to the Zone Master. Each zone can have only one Master.
The Master of zone 0 also controls the Masters and Slaves of the
other zones.
Set opening slow-down distance, choosing a percentage value
of the overhead door's whole travel.
Set closing slow-down distance, choosing a percentage value of
the overhead door's whole travel.
HYDRA N - 15