LED Housing Installation
WARNING: The luminaire must be grounded as required by the National Electrical Code (Paragraph 410-21 and Article 250) or
Canadian Electrical Code (Rule 30-500 and Section 10). Verify that ground continuity has been established by using an Ohm meter
or other suitable test equipment before energizing the luminaire. Failure to properly ground the luminaire will create an electric shock
hazard, which can cause serious injury or death.
This product is intended to be used with Eaton Crouse-Hinds Champ series mounting hoods. It is up to the installer to ensure that
the Crouse-Hinds mounting hood that this product is being installed on is in good condition and will mate with the luminaire properly.
Installer must ensure that the gasket is compressed properly against the Crouse-Hinds hood all the way around the luminaire.
Once this product is installed to a compatible Crouse-Hinds mounting hood it may not be removed from the hood as this is a
non-serviceable joint. To service the fixture the three captive bolts from the top side of the fixture may be removed to access the
electronic driver.
1. Disconnect facility power to the electric power supply leads.
2. Hang the LED housing on the hinge as shown in the figure above.
3. Connect the electric power supply leads to the cord that comes out of the luminaire. 12 inches of cord is provided from the top of
the fixture with stripped leads. If less cord is required the installer may cut shorter and re-strip wires.
4. Make sure hood is grounded to the luminaire by attaching ground wire to the cord provided.
5. Once wired, swing luminaire into position and tighten the captive bolt into the Crouse-Hinds hoods until the luminaire and mounting
hood bottoms out.
Appleton • 1.800.621.1506 • www.appletonelec.com
FIGURE 2: WIRING COMPARTMENT
650583-000 Rev. C 02/25/19 • Page 3 of 8